ES-7574 Rev.10

R5T-PC2

Remote I/O R5 Series

PULSE OUTPUT MODULE

(screw terminal block; photo MOSFET relay output, 2 points)

MODEL: R5T–PC2[1][2]

ORDERING INFORMATION

• Code number: R5T-PC2[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R5T-PC2W/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

NO. OF CHANNELS

2: 2-point outputs

[1] COMMUNICATION MODE

S: Single
W: Dual

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS

Connection
  Internal bus: Via the Installation Base (model: R5-BS)
  Output: M3.5 screw terminal block (torque 0.8 N·m)
  Internal power: Via the base (model: R5-BS)
Screw terminal: Nickel-plated steel (standard) or stainless steel
Isolation: Po 1 to Po 2 to internal bus or internal power
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
Output status indicator: Red LED; turns on with the outputs ON.
Pulse width adjustment: 5 msec., 10 msec., 50 msec., 100 msec., 500 msec., 1 sec., 1.5 sec., 2 sec. (Side DIP SW)
Count reset: Via DIP switches on the side

OUTPUT SPECIFICATIONS

Output: Photo MOSFET relay contact, 2 points
Common: Each point independent
Rated load: 125 V AC/DC @ 50 mA (resistive load)
Maximum ON resistance: 50 Ω
Maximum frequency: 100 Hz (DIP SW selectable)
Totalized pulse range: 1 – 10000 (‘0’ at reset)
(Max. pulse range selectable from 100 to 60000 using the R5CON PC Configurator Software. Refer to the R5CON Users Manual for detailed information.)
Count at overflow: Reset and restart at ‘1.’

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R5-BS)
Weight: 110 g (0.24 lb)

PERFORMANCE

Data allocation: 2
Response time: ≤ 0.1 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(Po 1 to Po 2 to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG;
isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive 
 EN 61010-1, EN 61010-2-201
 Measurement Category II (output)
 Pollution Degree 2
 Output to internal bus or internal power – Basic insulation (300 V)
RoHS Directive

FUNCTIONS

Counter reset
1) Remove Network Module or its cables and interrupt communication with other devices.
2) Turn ON the Counter Reset SW (SW8) on the module.
3) Return the module to the base and turn the power supply on.
4) Red RUN LED turns on and the module starts resetting its counter. When the resetting is complete, the LED light turns to green. DO NOT remove the power while the red light is on.
5) After the green LED is confirmed, turn the power supply off.
6) Turn OFF the Counter Reset SW (SW8).
7) Return the Network module onto the base and turn the power supply on.
Note: Counter Reset SW must be turned OFF after this procedure because the module does not start counting with ON state.

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM