ES-8934 Rev.4

R3S-RR8

Remote I/O R3 Series

REMOTE CONTROL RELAY CONTROL MODULE

(Do 8 points, tension clamp terminal block)
Functions & Features
• Controls remote control relays for lighting control with Fieldbus
• Applicable to the remote control relays already installed
• Monitors status of remote control relays with feedback inputs from signal lines
Typical Applications
• Monitors and controls of lighting in buildings
 

MODEL: R3S-RR8[1][2]

ORDERING INFORMATION

• Code number: R3S-RR8[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3S-RR8W/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS

8: 8

[1] COMMUNICATION MODE

S: Single
W: Dual

[2] OPTIONS

blank: none
/Q: Options other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Interface Module (model: R3-NC1, NC3, NE1, NM1, NDx, NF2, NFL1)
Firmware version V2.00 or higher.
R3-NF2 is available with firmware version V0.04 or higher.

GENERAL SPECIFICATIONS

Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Output: Separable tension clamp terminal (applicable wire size: 0.2 to 1.5 mm2, stripped length 10 mm)
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Output to internal bus or internal power
Input Data Length: 8 bit, 16 bit selectable with DIP switch
Output data length: 8 bit, 16 bit selectable with DIP switch
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED;
OFF in abnormality; ON in normal operating conditions.
Input output status indicator: Red LED;
  1 to 8: Output bit status, turns on with bit set ON.
  9 to 16: Feedback input status, turns on with the input ON.

OUTPUT SPECIFICATIONS

Number of output: 8 points
Common: All 8 points (12 terminal)
Rated load voltage: 24 V AC ±10 % (supplied by the remote control transformer)
Load voltage frequency: 50 / 60 Hz
Maximum outputs provided at once: No limit
Output ON duration: 100 msec.

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE

Data allocation: 1
Current consumption: 40 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

OUTPUT TERMINAL ASSIGNMENT

INPUT OUTPUT DATA BIT & DATA ALLOCATION