ES-8413 Rev.12

R3-DC64A

Remote I/O R3 Series

DISCRETE OUTPUT MODULE

(Do 64 points; open collector)

MODEL: R3–DC64A[1][2]

ORDERING INFORMATION

• Code number: R3-DC64A[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3-DC64AW/CE/Q) 
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS

64: 64

OUTPUT

A: Open collector

[1] COMMUNICATION MODE

S: Single
W: Dual

[2] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Output: 40-pin connector (OTAX N365P040AU
  (Fujitsu FCN-365P040-AU...discontinued))
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Do11 thru Do18 to Do21 thru Do28 to Do31 thru Do38 to Do41 thru Do48 to Do51 thru Do58 to Do61 thru Do68 to Do71 thru Do78 to Do81 thru Do88 to internal bus or internal power
Output hold setting: Setting for communication error with side DIP SW
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED turns on in normal operating conditions.
Output status indicator: Red LED; turns on with the output ON.
Group selector: Switches the output status indicator
CN1:
 A. 1 - 8: Do11 - Do18, 9 - 16: Do21 - Do28
 B. 1 - 8: Do31 - Do38, 9 - 16: Do41 - Do48
CN2:
 A. 1 - 8: Do51 - Do58, 9 - 16: Do61 - Do68
 B. 1 - 8: Do71 - Do78, 9 - 16: Do81 - Do88

OUTPUT SPECIFICATIONS

Output: Open collector, 64 points
Isolation: Optical isolator
Common: All 8 points (8 terminals)
Common current: Max. 1 A per common
External excitation: 24 V DC ±10 %, approx. 0.04 A
Rated load voltage: 24 V DC ±10 %
Maximum load current: 0.1 A per point
Maximum rush current: 0.5 A for max. 10 msec.
Maximum leak current at OFF: 0.1 mA
Maximum voltage drop at ON: 0.1 V DC typical; 1.2 V DC max.
(When driving an inductive load, connect a diode in parallel with the load.)

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 200 g (0.44 lb)

PERFORMANCE

Data allocation: 4
Current consumption: 160 mA
Response time: ≤ 2 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(Do 11 thru 18 to Do 21 thru 28 to Do 31 thru 38 to Do 41 thru 48 to Do 51 thru 58 to Do 61 thru 68 to Do 71 thru 78 to Do 81 thru 88)
2000 V AC @ 1 minute (output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FUNCTIONS

OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
Output Hold
If both are in error, the module holds the signal and stands by until one of the communications recovers.
Output OFF
If both are in error, the module outputs OFF signals and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

OUTPUT CONNECTOR (40-pin)