ES-8420 Rev.11

R3-BC32A

Remote I/O R3 Series

BCD CODE OUTPUT MODULE

(7-digit BCD; open collector)

MODEL: R3–BC32A[1][2]

ORDERING INFORMATION

• Code number: R3-BC32A[1][2]
Specify a code from below for each [1] and [2].
  (e.g. R3-BC32AW/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS

32: BCD code, 7 digits (4 channels/digit)

OUTPUT

A: Open collector

[1] COMMUNICATION MODE

S: Single
W: Dual

[2] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Output: 40-pin connector (OTAX N365P040AU
  (Fujitsu FCN-365P040-AU...discontinued))
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Do 11 thru 28 to Do 31 thru 48 to Do 51 thru 68 to Do 71 thru 88 to internal bus or internal power
Output hold setting: Setting for communication error with side DIP SW
Strobe signal control: Selectable with the side DIP switch.
Strobe signal output time: 5 ms, 10 ms, 50 ms and 100 ms selectable with the side DIP switch
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED turns on in normal operating conditions.
Output status indicator: Red LED; turns on with the output ON.
Group selector: Switches the output status indicator
 A. 1 - 8: Do11 - Do28
     9 - 16: Do31 - Do48
 B. 1 - 8: Do51 - Do68
     9 - 16: Do71 - Do88

OUTPUT SPECIFICATIONS

Output signal: Open collector, 32 points (4 points/digit)
Isolation: Optical isolator
Common: All 4 points (8 terminals)
Common current: Max. 1 A per common
External excitation: 24 V DC ±10 %, approx. 0.04 A
Rated load voltage: 24 V DC ±10 %
Maximum load current: 0.1 A per point
Maximum rush current: 0.5 A for max. 10 msec.
Maximum leak current at OFF: 0.1 mA
Maximum voltage drop at ON: 0.1 V DC typical; 1.2 V DC max.
(When driving an inductive load, connect a diode in parallel with the load.)
Number of digits: 7 with strobe signal, 8 without it
Data: 2 words
Data description example
Input data
: 1 2 3 4   5 6 7 8
                    high digits       low digits
Address 1: 5678 (4 low digits)
Address 2: 1234 (4 high digits)

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 150 g (0.33 lb)

PERFORMANCE

Data allocation: 4
Current consumption: 150 mA
Response time: ≤ 2 msec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
500 V AC @ 1 minute
(Do 11 thru 28 to Do 31 thru 48 to Do 51 thru 68 to Do 71 thru 88)
2000 V AC @ 1 minute
(Output to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FUNCTIONS

OUTPUT HOLD or OUTPUT OFF
In normal conditions, the module outputs the signal from the preferred bus A.
When an error is detected, the output is switched to the data from the bus B.
Output Hold
If both are in error, the module holds the signal and stands by until one of the communications recovers.
Output OFF
If both are in error, the module outputs OFF signals and stands by until one of the communications recovers.
At the startup, it outputs OFF until the communication is established and normal data is received.
STROBE SIGNAL CONTROL
Controls the timing of reading data. Strobe signal is output at every data output. Strobe signal cannot be supplied independently without data output.

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

OUTPUT CONNECTOR (40-pin)