ES-8419 Rev.10

R3-BA32A

Remote I/O R3 Series

BCD CODE INPUT MODULE

(7-digit BCD)

MODEL: R3–BA32A[1][2]

ORDERING INFORMATION

• Code number: R3-BA32A[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. R3-BA32AW/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

NO. OF CHANNELS

32: BCD code, 7 digits (4 channels/digit)

EXCITATION SUPPLY

A: External excitation, 24 V DC

[1] COMMUNICATION MODE

S: Single
W: Dual

[2] OPTIONS (multiple selections)

Standards & Approvals
blank: Without CE
/CE: CE marking
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Connection
  Internal bus
: Via the Installation Base (model: R3-BSx)
  Input: 40-pin connector (OTAX N365P040AU
  Fujitsu FCN-365P040-AU...discontinued))
  Internal power: Via the Installation Base (model: R3-BSx)
Isolation: Di 11 thru 28 to Di 31 thru 48 to Di 51 thru 68 to Di 71 thru 88 to internal bus or internal power
Strobe signal control: Selectable with the side DIP switch.
RUN indicator: Bi-color (red/green) LED;
Red when the bus A operates normally;
Green when the bus B operates normally;
Amber when both buses operate normally.
ERR indicator: Green LED turns on in normal operating conditions.
Input status indicator: Red LED; turns on with the input ON.
Group selector: Switches the input status indicator
 A. 1 - 8: Di11 - Di28
     9 - 16: Di31 - Di48
 B. 1 - 8: Di51 - Di68
     9 - 16: Di71 - Di88
Read rate: 5 / 10 / 50 / 100 msec. selectable with DIP SW

INPUT SPECIFICATIONS

Number of digits: 7 with strobe signal, 8 without it
Data: 2 words
Data description example
  Input data
: 1 2 3 4  5 6 7 8
                     4 high digits      4 low digits
  Address 1: 5678 (4 low digits)
  Address 2: 1234 (4 high digits)
Input signal: 24 V DC, 32 points (4 points/digit)
Input resistance: 6 kΩ
Isolation: Optical isolator
Common: 4 positive/negative commons, per 8 points
Contact detecting: 24 V DC ±10 %, approx. 4 mA
ON current/resistance: ≥ 2 mA, ≤ 2 kΩ
OFF current/resistance: ≤ 1 mA, ≥ 18 kΩ

INSTALLATION

Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R3-BSx)
Weight: 150 g (0.33 lb)

PERFORMANCE

Data allocation: 4
Current consumption: 90 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
500 V AC @ 1 minute
(Di 11 thru 28 to Di 31 thru 48 to Di 51 thru 68 to Di 71 thru 88)
2000 V AC @ 1 minute
(Input to internal bus or internal power)
2000 V AC @ 1 minute (power input to FG; isolated on the power supply module)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

FUNCTIONS

STROBE SIGNAL CONTROL
Controls the timing of reading data. Data is read in when the strobe signal is ON. No data read while it is OFF, even if there is a status change.

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

INPUT CONNECTOR (40-pin)