ES-6701 Rev.6

R2K-1

R2K Series

RS-232-C/RS-485 CONVERTER

Functions & Features
• Bidirectional converter between RS-232-C and RS-485 used when connecting Modbus RS-485 devices to a PC

MODEL: R2K-1-[1]

ORDERING INFORMATION

• Code number: R2K-1-R
Consult Factory for AC power input.

[1] POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS

Connection
  RS-232-C: 9-pin D-sub connector (male, lock screw No. 4-40 UNC); A ‘Straight’ type cable connecting to the PC is to be prepared by the user.
  RS-485, power input: Euro type connector terminal
Isolation: RS-232-C to RS-485 or power
Data, parity & stop bit setting: DIP switches at the bottom
Baud rate setting: Front rotary switch
RUN indicator LED: Green light blinks in normal conditions.
ERR.1 indicator: Red LED blinks with RS-232-C overrun error; ON with parity framing error.
ERR.2 indicator: Red LED blinks with RS-485 overrun error; ON with parity framing error.

COMMUNICATION

Baud rate: 300, 600, 1200, 2400, 4800, 9600, 14.4 k,
19.2 k, 28.8 k, 38.4 k, 57.6 k, 76.8 k (bps)
Data bit: 7 or 8 bits
Parity: Odd, even or none
Stop bit: 1 or 2 bits
Communication: Half-duplex, asynchronous, no procedure
Data delay time: 300 microseconds
RS-232-C
Standard
: Conforms to RS-232-C, EIA
Transmission distance: 10 meters max.
RS-485
Standard
: Conforms to TIA/EIA–485–A
Transmission distance: 500 meters max.
Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.)

INSTALLATION

Power consumption
DC: Approx. 2 W
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(RS-232-C to RS-485 or power)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM