ES-1379 Rev.14

MFS

Plug-in Signal Conditioners M-UNIT

SPLIT-RANGE TRANSMITTER

Functions & Features
• Generating two signals which control two final control elements
• High-density mounting
Typical Applications
• Balancing two final control elements in opposite actions used in heating-cooling or humidifying-dehumidifying processes
 

MODEL: MFS–[1]–[2][3][4]–[5][6]

ORDERING INFORMATION

• Code number: MFS-[1]-[2][3][4]-[5][6]
Specify a code from below for each of [1] through [6].
  (e.g. MFS-V-AAA-B/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

[1] OUTPUT CHARACTERISTICS

V: V-shape
P: Parallel
Output 2 is assigned to the reversed output in V-shape characteristics.

[2] INPUT

Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
4: 0 – 10 V DC (Input resistance 200 kΩ min.)
I/O code combination avaliable AAA or 444 suffix codes only.

[3] OUTPUT 1

Current
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
4: 0 – 10 V DC (Load resistance 10 kΩ min.)

[4] OUTPUT 2

Current
A: 4 – 20 mA DC (Load resistance 600 Ω max.)
Voltage
4: 0 – 10 V DC (Load resistance 10 kΩ min.)

[5] POWER INPUT

AC Power
B: 100 V AC
C: 110 V AC
D: 115 V AC
F: 120 V AC
G: 200 V AC
H: 220 V AC
J: 240 V AC
DC Power
R: 24 V DC

[6] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3.5 screw terminals
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input or output 1 or output 2 to power
Input range: 0 – 23.2 mA DC or -1 – +12 V DC
Output range: 0 – 23.2 mA DC or -1 – +12 V DC
Output characteristics
 V-shape: two signals vary in opposite directions; used when both final control devices have the same action (direct-direct or reverse-reverse).
 Parallel: two signals vary in the same direction; used when one final control device is direct and another is reverse.
Monitor jacks: Direct monitoring of output signal; accessible at front
Ammeter requirement: Input resistance 10 Ω max. (for current output)
Monitor jack diameter: 2 mm (.08")

INPUT SPECIFICATIONS

DC Current: Input resistor incorporated

INSTALLATION

Power input
AC: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 3 VA
DC: Operational range: 24 V ±10 %,
approx. 80 mA (ripple 10 %p-p max.)
Operating temperature: -5 to +60°C (23 to 140°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 400 g (0.88 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.3 % (gain = 1 or -1)
Temp. coefficient: ±0.02 %/°C (±0.01 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute (input or output 1 or output 2 to power to ground)

EXTERNAL VIEW

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

OPERATION DIAGRAM