ES-9289 Rev.7

MDC7

DC POWER SUPPLY

(maintenance forecast monitor function, capacity 240 W)
Functions & Features
• Accepts 100 – 240 V AC and provides regulated 24 V DC output
• Maintenance forecast monitor function

MODEL:MDC7–24024A–M2

ORDERING INFORMATION

• Code number: MDC7-24024A-M2

CAPACITY

240: 240 W

OUTPUT VOLTAGE

24: 24 V DC

MONITOR

A: Maintenance forecast monitor function

POWER INPUT

AC Power
M2: 100 – 240 V AC

GENERAL SPECIFICATIONS

Construction: Front terminal access; terminal cover provided
Connection
 Power input, output voltage: M4 screw terminals (torque 1.08 N·m)
 Alarm output: Applicable wire size: 0.081 to 0.823 mm2, stripped length: 9 to 10 mm
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (beige); aluminum

SUPPLY OUTPUT

Output voltage: 24 V DC -10/+15 %; adjustable on the front (ripple 2.0 %p-p max.)
Load current: ≤ 10 A
Overload protection: Voltage drop characteristics (105 %)
Overload detecting: 105 % of the rated current
Alarm Output
Transistor: NPN (sink) type; 30 V DC max., 50 mA DC max.
Residual voltage at ON: ≤ 2 V
Leakage current at OFF: ≤ 0.1 mA

INSTALLATION

Power input
AC: Operational voltage range 85 – 264 V AC  50/60 Hz
Operating temperature: 0 to 50°C (32 to 122°F)
Operating humidity: 25 to 85 % RH (non-condensing)
Mounting: DIN rail
Weight: 1150 g (2.54 lb)

PERFORMANCE

Temp. coefficient: ±0.05 %/°C (±0.03 %/°F)
Load effect: ≤ 1.5 %
Line voltage effect: ±0.5 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 3000 V AC @ 1 minute
(output voltage or alarm output to power input)
2000 V AC @ 1 minute (power input to ground)
1000 V AC @ 1 minute (output voltage or alarm output to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EN 61204-3 (Class A)
Low Voltage Directive
  EN 62477-1
RoHS Directive
Approval:
  UL 508 (Class 2: per UL 1310)
  CAN/CSA C22.2 No.14

EXTERNAL VIEW

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

CONNECTION DIAGRAM