·Some details are not shown. Please refer to specification sheets for all information.

18YVT

Rack-mounted DCS Signal Conditioners 18-RACK

VOLTAGE GENERATOR
(for testing)

Functions & Features
• Generating DC voltage signals
• Output voltages are easily adjustable
Typical Applications
• Generated voltages can be used for function checks of the entire control system

MODEL: 18YVT–066–R

ORDERING INFORMATION
• Code number: 18YVT-066-R

INPUT
0: None

OUTPUT 1
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)

OUTPUT 2
Voltage
6: 1 – 5 V DC (Load resistance 2000 Ω min.)

POWER INPUT
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS
Construction: Rack-mounted; terminal access via screw terminals on the front and connector on the rear; terminal cover provided
Connection
  Output 1 & 2
: Connector
  Monitor output: M3.5 screw terminals (torque 0.8 N·m)
  Power input: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Output to power
(all outputs internally connected)

OUTPUT SPECIFICATIONS
Output: 1 – 5 V DC
Output adjustment: 270°-turn screwdriver (front)

INSTALLATION
Power consumption
DC: Approx. 15 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 18BXx or 18KBXx
Weight: 150 g (0.33 lbs)

PERFORMANCE in percentage of span
Line voltage effect: ±0.5 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute (output to power)
1500 V AC @ 1 minute (output or power to ground)

EXTERNAL VIEW

DIMENSIONS unit: mm (inch)

TERMINAL ASSIGNMENTS

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.