ES-5028 Rev.8

M2DU

Super-mini Signal Conditioners Mini-M Series

CURRENT LOOP SUPPLY

(10 – 50 mA loop)
Functions & Features
• Powering a 10 – 50 mA DC current loop
• Isolation
• Shortcircuit protection
• Universal power input
• High-density mounting
Typical Applications
• Various 2-wire transmitters

MODEL: M2DU–24-[1][2]

ORDERING INFORMATION

• Code number: M2DU-24-[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. M2DU-24-M/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01)

SUPPLY OUTPUT

24: 24 V DC

INPUT

Current
10 – 50 mA DC (Input resistance  approx. 100 Ω)

OUTPUT

Voltage
1-5 V DC (Load resistance  50 kΩ min.)

[1] POWER INPUT

AC Power
M: 85 – 264 V AC (Operational voltage range 85 – 264 V,
47 – 66 Hz)
DC Power
R2: 11 – 27 V DC
(Operational voltage range 11 – 27 V, ripple 10 %p-p max.)
P: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
/C04: Polyolefin coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel

GENERAL SPECIFICATIONS

Construction: Plug-in
Connection: M3 screw terminals (torque 0.8 N·m)
Screw terminal: Chromated steel (standard) or stainless steel
Housing material: Flame-resistant resin (black)
Isolation: Input to output to power
Overrange output: Approx. -10 to +120 %
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

SUPPLY OUTPUT

Output voltage: 24 – 28 V DC with no load
Current rating: ≤ 55mA DC
Shortcircuit Protection
Current limited
: ≤ 65 mA
Protected time duration: No limit

INPUT SPECIFICATIONS

DC Current: Input resistor incorporated

INSTALLATION

Power Consumption
AC: Approx. 5 VA
DC: Approx. 3 W
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 150 g (0.33 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
Temp. coefficient: ±0.015 %/°C (±0.008 %/°F)
Response time: ≤ 0.5 sec. (0 – 90 %)
Line voltage effect
  Supply output: ±3 % over voltage range
  Output signal: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @1 minute  (input to output to power to ground)

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM