ES-1573 Rev.9
JTY2
Plug-in Signal Conditioners M-UNIT
PULSE DURATION RECEIVER
(field-programmable; built-in excitation)
Functions & Features
• Converts the pulse duty ratio into a standard process signal
• Built-in excitation
• Field-selectable input type and range: Dry contact, voltage pulse or two-wire current pulse
• Isolation up to 2000 V AC
• High-density mounting
Typical Applications
• Transmission or telemetering
• Converting the pulse duty ratio into an analog momentary values
MODEL: JTY2–[1][2]–[3][4]
ORDERING INFORMATION
• Code number: JTY2-[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
(e.g. JTY2-76-K/Q)
• Special output range (For codes Z & 0)
• Use Ordering Information Sheet (No. ESU-1573). Factory setting (table below) will be used if not otherwise specified.
• Specify the specification for option code /Q
(e.g. /C01/S01)
INPUT – Field-selectable
Open collector
Voltage pulse
Two-wire current pulse
Described accuracy may not be assured when the input waveform is not clear.
[1] EXCITATION
1
: 5 V DC @ 120 mA
4
: 12 V DC @ 60 mA
7
: 24 V DC @ 25 mA
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C
: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D
: 0 – 20 mA DC (Load resistance 750 Ω max.)
E
: 0 – 16 mA DC (Load resistance 900 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 100 Ω min.)
4
: 0 – 10 V DC (Load resistance 1000 Ω min.)
5
: 0 – 5 V DC (Load resistance 500 Ω min.)
6
: 1 – 5 V DC (Load resistance 500 Ω min.)
4W
: -10 – +10 V DC (Load resistance 2000 Ω min.)
5W
: -5 – +5 V DC (Load resistance 1000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
[3] POWER INPUT
AC Power
K
: 85 – 132 V AC
DC Power
S
: 12 V DC
R
: 24 V DC
V
: 48 V DC
P
: 110 V DC
[4] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
RELATED PRODUCTS
• Programming Unit (model: PU-2x)
• PC configurator software (model: JXCON)
Downloadable at our web site.
A dedicated cable is required to connect the module to the PC. Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to DC output to alarm output to power
Overrange output
: Approx. -15 to +115 % at 1 – 5 V
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Alarm mode
: High or Low
Alarm setpoint
: -15 – +115 %
Alarm deadband
: 0 – 20 %
Linearization
: Max. 16 points
Input monitor LED
: Red LED blinks according to the input.
Excitation adjustment
: 5 – 24 V DC
Software programming
: Programming Unit (model: PU-2x);
(Refer to the users manual of JXCON for the adjustments configurable with JXCON)
• Input zero and span duty ratio
• No input detecting time
• Moving average
• Alarm setpoint
• Output fine adjustment
• Linearization
• Others
Adjustments
: With DIP and Rotary switches.
• Pulse amplitude
• Input type
(Refer to the instruction manual for details)
Modular jack
: Connecting the PU-2x
Input pulse sensing
: DC coupled
No input detecting
: The output forced to 0 % or 100 % when no input is provided for a preset time period.
INPUT SPECIFICATIONS
Excitation
: Shortcircuit protection; approx. 440 mA (max.) at shortcircuit
Frequency
: 0.1 – 1000 Hz
(max. 500 Hz for open collector input)
Duty ratio range
: 1 – 99 % (including 0 and 100 %)
Minimum span
: 20 % (span duty ratio – zero duty ratio)
■
Open Collector
Input requirements
:
(Excitation: Sensing)
5 V: Approx. 4 V / 1.0 mA
12 V: Approx. 9 V / 2.3 mA
24 V: Approx. 16 V / 4.7 mA
ON resistance
: ≤ 200 Ω
OFF resistance
: ≥ 200 kΩ
Detecting level
: 0 – 5 V
(Readjustment is required to match the duty ratio after the sensor excitation, the pulse amplitude have been changed.)
Detecting pulse edge
: OFF (input monitor LED ON) to ON (LED OFF) and ON to OFF
■
Voltage Pulse
Waveform
: Square
Input impedance
: 10 kΩ min.
Pulse amplitude
: 0.1 – 100 Vp-p
Max. voltage between input terminals
: 50 V
Detecting level
: 0 – 5
(Readjustment is required to match the duty ratio after the pulse amplitude have been changed.)
Detecting pulse state
: A pulse rise detected when the input voltage goes above the detecting level (input monitor LED ON); a pulse sink detected when it goes below the level (LED OFF).
■
Two-wire Current Pulse
Waveform
: Square
Input resistance
: Receiving resistor 100 Ω
Input range
: 0 – 25 mA
Minimum pulse amplitude
: 10 mA
Detecting level
: 0 – 5 V
(Readjustment is required to match the duty ratio after the pulse amplitude have been changed.)
Detecting pulse state
: The input resistor (100 Ω) converts the current signal into 0 – 2.5 V. A pulse rise detected when the voltage goes above the detecting level (input monitor LED ON); a pulse sink detected when it goes below the level (LED OFF).
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 15 V max.
■
DC Voltage
: -10 – +12 V DC
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 10 mA max.; 5 mA for negative voltage output; at ≥ 0.5 V
■
Alarm Output
: Relay contact
Rated load
: 125 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage
: 250 V AC or 125 V DC
Maximum switching power
: 62.5 VA or 60 W
Minimum load
: 10 mV DC @ 1 mA
Mechanical life
: 5 × 10
7
cycles (300 cycles/minute)
For maximum relay life with inductive loads, external protection is recommended.
INSTALLATION
Power input
•
AC
: Operational voltage range 85 – 132 V,
47 – 66 Hz, approx. 6 VA
•
DC
: Operational voltage range: Rating ±10 %, or 85 – 150 V for 110 V rating; ripple 10 %p-p max.; Approx. 3.3 W (130 mA at 24 V)
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 350 g (0.77 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.25 %
Alarm setpoint accuracy
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: 0.5 sec. + 1 pulse cycle (0 – 90 %)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
:
2000 V AC @ 1 minute (input to output to power)
1500 V AC @ 1 minute (input or output or power to alarm output)
2000 V AC @ 1 minute (circuit to ground)
EXTERNAL VIEW
Refer to the instruction manual for detailed procedures.
INPUT PULSE LOGIC
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM