ES-5412 Rev.9
F2TS
Super-mini Signal Conditioners F2 Series
THERMOCOUPLE TRANSMITTER
Functions & Features
• Accepting direct input from a thermocouple and providing a standard process signal
• 5-segment linearization
• Burnout protection
• High-accuracy cold junction compensation
• Fast response type available
• High-density mounting
Typical Applications
• High-accuracy cold junction compensation benefits narrow span measurements
• 0.1 μA burnout sensing enables long distance transmission with minimum offset drifts
• Electric furnace (isolation)
• No burnout type can connect to a single T/C in parallel with a recorder
MODEL: F2TS-[1][2]-R[3]
ORDERING INFORMATION
• Code number: F2TS-[1][2]-R[3]
Specify a code from below for each of [1] through [3].
(e.g. F2TS-2A-R/BL/CE/Q)
• Temperature range (e.g. 0 – 800°C)
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01)
[1] INPUT THERMOCOUPLE
2
: K (CA) (Usable range -270 to +1370°C, -454 to +2498°F)
4
: J (IC) (Usable range -210 to +1200°C, -346 to +2192°F)
5
: T (CC) (Usable range -270 to +400°C, -454 to +752°F)
7
: R (Usable range -50 to +1760°C, -58 to +3200°F)
8
: S (Usable range -50 to +1760°C, -58 to +3200°F)
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C
: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D
: 0 – 20 mA DC (Load resistance 750 Ω max.)
E
: 0 – 16 mA DC (Load resistance 900 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 1000 Ω min.)
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS (multiple selections)
Response Time (0 – 90 %)
blank
: Standard (≤ 0.5 sec.)
/K
: Fast Response (Approx. 25 msec.)
Burnout
blank
: Upscale burnout
/BL
: Downscale burnout
/BN
: No burnout
Standards & Approvals (must be specified)
/N
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: Option other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
GENERAL SPECIFICATIONS
Construction
: Stand-alone; terminal access at the front
Connection
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Linearization
: Standard
Cold junction compensation
: CJC sensor attached to the
input terminals
INPUT SPECIFICATIONS
Offset
: Max. 1.5 times span
Input resistance
: 30 kΩ min.
Burnout sensing
: 0.1 μA
Minimum span (in °C)
K (CA)
: min. span 75°C
J (IC)
: min. span 100°C
T (CC)
: min. span 200°C
R
: min. span 1600°C
S
: min. span 1000°C
Minimum span (in °F)
K (CA)
: min. span 140°F
J (IC)
: min. span 180F
T (CC)
: min. span 360°F
R
: min. span 2880°F
S
: min. span 1800°F
Note: The described accuracy may be partially not satisfied when the temperature ranges below 0°C. Consult factory.
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 15 V max.
■
DC Voltage
: -10 – +12 V DC
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 1 mA max.; at ≥ 0.5 V
INSTALLATION
Current consumption
•
DC
: Approx. 80 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail
Weight
: 150 g (0.33 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.4 % (at over 400°C or 750°F for R and S)
Cold junction compensation error
(at 20°C ±10°C or 68°F ±18°F)
K, J, T
: ±1°C or ±1.8°F
S, R
: ±2°C or ±3.6°F
Temp. coefficient
: ±0.09 %/°C (±0.05 %/°F)
(at over 400°C or 750°F for R and S)
Burnout response
: ≤ 10 sec.
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM