ES-5434 Rev.8
F2SP
Super-mini Signal Conditioners F2 Series
LOW FREQUENCY TRANSMITTER
(50 Hz minimum)
Functions & Features
• Converting the output from a pulse-type transducer into a standard process signal
Typical Applications
• Positive displacement flowmeters, turbine flowmeters and vortex flowmeters
• Proximity switches
MODEL: F2SP–[1][2]–R[3]
ORDERING INFORMATION
• Code number: F2SP-[1][2]-R[3]
Specify a code from below for each of [1] through [3].
(e.g. F2SP-2A-R/CE/Q)
• Frequency range (e.g. 0 – 10 kHz)
• Special output range (For codes Z & 0)
• Specify the specification for option code /Q
(e.g. /C01)
[1] INPUT
1
: Dry contact
2
: Voltage pulse
[2] OUTPUT
Current
A
: 4 – 20 mA DC (Load resistance 750 Ω max.)
B
: 2 – 10 mA DC (Load resistance 1500 Ω max.)
C
: 1 – 5 mA DC (Load resistance 3000 Ω max.)
D
: 0 – 20 mA DC (Load resistance 750 Ω max.)
E
: 0 – 16 mA DC (Load resistance 900 Ω max.)
F
: 0 – 10 mA DC (Load resistance 1500 Ω max.)
G
: 0 – 1 mA DC (Load resistance 15 kΩ max.)
Z
: Specify current (See OUTPUT SPECIFICATIONS)
Voltage
1
: 0 – 10 mV DC (Load resistance 10 kΩ min.)
2
: 0 – 100 mV DC (Load resistance 100 kΩ min.)
3
: 0 – 1 V DC (Load resistance 1000 Ω min.)
4
: 0 – 10 V DC (Load resistance 10 kΩ min.)
5
: 0 – 5 V DC (Load resistance 5000 Ω min.)
6
: 1 – 5 V DC (Load resistance 5000 Ω min.)
0
: Specify voltage (See OUTPUT SPECIFICATIONS)
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
GENERAL SPECIFICATIONS
Construction
: Stand-alone; terminal access at the front
Connection
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output to power
Zero adjustment
: -5 to +5 % (front)
Span adjustment
: 95 to 105 % (front)
Input pulse sensing
: DC coupled; detecting pulse rise
Input filter
: Provided with input range <100 Hz with dry contact input
(time constant approx. 1 msec.)
Low-end cutout
: 2 to 5 %
INPUT SPECIFICATIONS
Excitation
: 12 V DC @30 mA; shortcircuit protection
Frequency range
: 0 – 50 Hz through 10 kHz
•
Dry Contact
: Mechanical contact or open collector
Pulse width time requirement
: 20 μsec. min. for ON and
OFF (2 msec. for ranges <100 Hz)
Sensing
: Approx. 12V DC @3 mA
ON/OFF level
: ≤200 Ω/0.6 V for ON, ≥100k Ω/6 V for OFF
•
Voltage Pulse
: Square or sine waveforms
Pulse width time requirement
: 20 μsec. min. for high and low levels
Voltage range
: -30 – +30 V DC
Hi level
: 2 – 30 V p-p
Lo level
: ≤1 V
Input impedance
: 10k Ω minimum
OUTPUT SPECIFICATIONS
■ DC Current
: 0 – 20 mA DC
Minimum span
: 1 mA
Offset
: Max. 1.5 times span
Load resistance
: Output drive 15 V max.
■
DC Voltage
: 0 – 12 V DC
Minimum span
: 5 mV
Offset
: Max. 1.5 times span
Load resistance
: Output drive 1 mA max.; at ≥ 0.5 V
INSTALLATION
Current consumption
•
DC
: Approx. 80 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail
Weight
: 150 g (0.33 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 % (output 10 – 100 %)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: (0 – 90%)
Approx. 1.8 sec. with 0 – 50 Hz
Approx. 0.8 sec. with 0 – 100 Hz
Approx. 0.5 sec. with 0 – 500 Hz
Approx. 0.5 sec. with 0 – 10 kHz
Ripple
: 0.2 %p-p max. with input ≥ 10 %
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]