Super-mini Signal Conditioners F2 Series

INPUT LOOP POWERED ISOLATOR

Functions & Features
• Loop-powered design eliminates output loop power supply
• Two isolators housed in one enclosure
• 350 Ω output drive with 4 – 20 mA
Typical Applications
• Isolation between control room and field instrumentation, between telemetering system and input device
• Eliminates ground problems in existing systems
thanks to easiness of application without requiring additional power wiring

MODEL: F2SN–[1][2][3][4]

ORDERING INFORMATION

• Code number: F2SN-[1][2][3][4]
Specify a code from below for each of [1] through [4].
  (e.g. F2SN-2AA/CE/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] NO. OF CHANNELS

1: 1 channel
2: 2 channels

[2] INPUT

Current
A: 4 – 20 mA DC
H: 10 – 50 mA DC

[3] OUTPUT

Current
A: 4 – 20 mA DC
Voltage
6: 1 – 5 V DC

[4] OPTIONS (multiple selections)

Standards & Approvals (must be specified)
/N: Without CE
/CE: CE marking
Other Options
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating

GENERAL SPECIFICATIONS

Construction: Stand-alone; terminal access at the front
Connection: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm2, stripped length 7 mm)
Housing material: Flame-resistant resin (black)
Isolation: Input to output; between channels
Zero adjustment (front)
  Voltage output: -3 % to +3 %
  Current output: -0.5 % to +0.5%
Span adjustment (front)
  Voltage output
:  95 to 105 %
  Current output: 98.5 to 101.5 %

INPUT & OUTPUT

■ Input 4 – 20 mA DC / Output 1 – 5 V DC
Equivalent input impedance
: Approx. 250 Ω with 20 mA input
Operational range: 3 – 22 mA DC
(Accuracy is assured within 4 – 22 mA)
Load resistance: ≥ 50 kΩ

■ Input 10 – 50 mA DC / Output 1 – 5 V DC
Equivalent input impedance
: Approx. 100 Ω with 50 mA input
Operational range: 7 – 55 mA DC
(Accuracy is assured within 8 – 55 mA)
Load resistance: ≥ 50 kΩ

■ Input 4 – 20 mA DC / Output 4 – 20 mA DC
Equivalent input impedance
: 230 Ω plus load resistance with 20 mA input
Operational range: 3 – 22 mA DC
(Accuracy is assured within 4 – 22 mA)
Load resistance: 50 – 350 Ω (min. 50 Ω required for adequate operation)

■ Input 10 – 50 mA DC / Output 4 – 20 mA DC
Equivalent input impedance
: 90 Ω + [load resistance×0.16]  with 50 mA input
Operational range: 7 – 55 mA DC
(Accuracy is assured within 8 – 55 mA)
Load resistance: 50 – 600 Ω (min. 50 Ω required for adequate operation)
•INPUT 4 – 20 mA DC / OUTPUT 1 – 5 V DC
•INPUT 10 – 50 mA DC / OUTPUT 1 – 5 V DC
•INPUT 4 – 20mA DC / OUTPUT 4 – 20 mA DC
•INPUT 10 – 50 mA DC / OUTPUT 4 – 20 mA DC

INSTALLATION

Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: DIN rail
Weight: 150 g (0.33 lb)

PERFORMANCE in percentage of span

Accuracy: ±0.1 %
Temp. coefficient
  Voltage output: ±0.015 %/°C (±0.008 %/°F)
  Current output: ±0.02 %/°C (±0.01 %/°F)
Response time
  Voltage output
: ≤ 0.5 sec. (0 – 90 %) 
  Current output
  4 - 20 mA DC input
: Approx. 25 msec. (0 – 90 %, 50 Ω load) 
  10 - 50 mA DC input: Approx. 7 msec. (0 – 90 %, 50 Ω
  load)
Load effect (current output)
  4 – 20 mA input
: 0.015 %/Ω (50 – 150 Ω)
  0.003 %/Ω (150 – 350 Ω)
  10 – 50 mA input: 0.015 %/Ω (50 – 100 Ω)
  0.003 %/Ω (100 – 600 Ω)
(The unit is calibrated with 250 Ω load at the factory.)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
500 V AC @1 minute (input to output)
2000 V AC @1 minute (between channels)
2000 V AC @1 minute (input or output to ground)

STANDARDS & APPROVALS

EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive