ES-5422 Rev.8
F2D
Super-mini Signal Conditioners F2 Series
CURRENT LOOP SUPPLY
(non-isolated)
Functions & Features
• Powers a 4 – 20 mA DC current loop
• Electrically isolating output signal from power input
• Shortcircuit protection
• Applicable to smart transmitters
Typical Applications
• Various 2-wire transmitters
MODEL: F2D–24–R[1]
ORDERING INFORMATION
• Code number: F2D-24-R[1]
Specify a code from below for [1].
(e.g. F2D-24-R/CE/Q)
• Specify the specification for option code /Q
(e.g. /C01)
SUPPLY OUTPUT
24
: 24 V DC
INPUT
Current
4 – 20 mA DC (Input resistance 250 Ω)
OUTPUT 1
Voltage
1 – 5 V DC (Load resistance 250 kΩ min.)
OUTPUT 2
Current
4 – 20 mA DC
POWER INPUT
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[1] OPTIONS (multiple selections)
Standards & Approvals (must be specified)
/N
: Without CE
/CE
: CE marking
Other Options
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
GENERAL SPECIFICATIONS
Construction
: Stand-alone; terminal access at the front
Connection
: Euro type connector terminal
(applicable wire size: 0.2 to 2.5 mm
2
, stripped length 7 mm)
Housing material
: Flame-resistant resin (black)
Isolation
: Input or output to power
SUPPLY OUTPUT
Output voltage
: 24 – 28 V DC with no load
Current rating
: ≤ 22 mA DC
•
Shortcircuit Protection
Current limited
: 35 mA max.
Protected time duration
: No limit
INPUT SPECIFICATIONS
■
DC Current
: Input resistor incorporated
INSTALLATION
Current consumption
•
DC
: Approx. 80 mA
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail
Weight
: 150 g (0.33 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 % (accuracy of the receiving resistor)
Temp. coefficient
: ±0.003 %/°C (±0.002 %/°F) (temp. coefficient of the receiving resistor)
Line voltage effect to supply output
: ±3 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input or output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EMI EN 61000-6-4
EMS EN 61000-6-2
RoHS Directive
EXTERNAL DIMENSIONS unit: mm [inch]
TERMINAL ASSIGNMENTS unit: mm [inch]