ES-6512 Rev.14

DLC

Remote I/O

REMOTE I/O INTERFACE UNIT

Functions & Features
• Interfacing between the host computer and remote I/O devices
• RS-232-C (non-procedure)
• Buffer memory common for DLC commands enables quick I/O without waiting time
• Process I/O
 

MODEL: DLC–[1][2]–[3]

ORDERING INFORMATION

• Code number: DLC-[1][2]-[3]
Specify a code from below for each of [1] through [3].
  (e.g. DLC-1S1A4B4-K)

[1] TRANSMISSION MEDIA

1: Twisted-pair cable
2: Fiber optics cable
7: Twisted-pair – fiber optics (repeater incorporated)

[2] I/O SECTION

[Computer Interface without Process I/O]
00: RS-232-C (non-procedure)
[RS-232-C with Process I/O]
A1: Di 32 points
A2: Di 64 points
C1: Do 32 points (relay)
C2: Do 32 points (open collector)
C3: Do 64 points (relay)
C4: Do 64 points (open collector)
E1: Di 16 + Do 16 points (relay)
E2 : Di 16 + Do 16 points (open collector)
G1x: Ai 32 points
M1x: Ao 32 points
P1x : Pi 16 + Ai 16 points
R1xx: Ai 16 + Ao 16 points
S1xx: Ai 8 + Ao 8 + Di 8 + Do 8 points
U1x : Po 16 + Ao 16 points
See data sheet for Standard Multi-Transmission Unit (model: DLA1) for specifications of I/O sections.

[3] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L: 170 – 264 V AC
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
S: 12 V DC
(Operational voltage range 12 V ±10 %, ripple 10 %p-p max.)
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

RELATED PRODUCTS

• Standard multi-transmission unit (model: DLA1)

GENERAL SPECIFICATIONS

Construction: Surface mounting; terminal access on the front
Connection
  Transmission line terminal
: Euro type connector terminal; wire size 1.25 mm2 max.
  Power supply terminal: Euro type connector terminal; wire size 1.25 mm2 max.
  RUN contact output: Euro type connector terminal; wire size 1.25 mm2 max.
  I/O section
  •32-point I/O (or less): 40-pin connector terminal; M3 × 6 screws (torque 0.7 N·m)
  •64-point I/O: FCN 40-pin connector (two);
OTAX N365P040AU
(FUJITSU FCN-365P040-AU)
Housing material: Flame-resistant resin (beige)
Isolation: I/O to transmission section to power
Station No. setting: 2 rotary switches; 00 – FF (256)
Controller & Transmission Sections
Power indicator
: Red LED turns ON in normal conditions; OFF when the voltage level becomes low.
RUN indicator: Red LED turns OFF in error.
I/O Section
Contact I/O indicator LED
: Red lights turn on when the respective I/O channels are ON.
Analog I/O CPU RUN indicator LED: Red LED turns ON when the CPU function proves normal, OFF in error.
RUN Contact Output: Contact opens in error.
Rated load: 100 V AC or 30 V DC @ 1 A (resistive load)
Maximum switching voltage: 120 V AC or 30 V DC
Maximum switching power: 100 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Error detection
•Communication
: The receiver units detect loss of communication and wire break.
•CPU: Watch-dog timer
•Power voltage: Detects when the voltage supply to the CPU drops by 10 %.

MULTIPLEX COMMUNICATION

Communication: Half-duplex, synchronous
Transmission: Conform to RS-422, EIA
Transmission speed: 125 kbps
Protocol: SIN-NET (dedicated; data format conforms to SDLC)
Error check: CRC
Twisted-pair Cable
Cable
: CPEV-0.9 dia.
Connection: Euro Type connector terminal
(Applicable wire size: ≤ 1.25 mm2, stripped length 8 mm)
Transmission Distance: 1 kilometer max. with 16 units connected; 3 kilometers max. between 2 stations each of which consists of 3 units
Terminator: Incorporated (Remove the attached jumper pin when the unit is not located at the end of transmission line.)
Fiber Optics Cable
Link
: JIS F07 connector (Consult factory for details)
Transmission distance: 1 kilometer max. with PCF
Transmission loss: 7 dB max.
Twisted-pair – Fiber Optics: Converting signals between two media and waveform shaping

INTERFACE

Transmission: Conform to EIA RS-232-C
Communication: Asynchronous, half-duplex, non-procedure
DIP switch: Setting RS-232-C specifications
Transmission speed: 300 – 9600 bps
Data bit: 7 or 8 bits
Stop bit: 1, 1.5 or 2 bits
Parity: Even or odd
RS-232-C connector: 25-pin D-sub connector (female) (M2.6 × 0.45 screw connector)
RS-232-C cable: Cross (provided by the user)

INSTALLATION

Power consumption
AC: Approx. 17.5 VA
DC: Approx. 17 W (1.1 A with 24 V)
Grounding: Not required in normal environments; 100 Ω or less grounding resistance in noisy environments
Operating temperature: -5 to + 50°C (23 to 122°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface; Rack Mounting Frame (model: BX-1DL) available
Weight: 2 kg (4.4 lb)

PERFORMANCE

Permissible power failure duration
AC: ≤ 20 ms
DC: ≤ 1 ms
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(I/O to transmission to power)

DESCRIPTIONS

RUN Contact (LED) Behaviors
Input units (00, A1, A2, G1 and P1)
: The LED turns ON with the network configured; OFF in an abnormality; the network is reconfigured after an abnormality.
Output units (C1, C2, C3, C4, M1 and U1): The LED turns ON when data from the paired input unit is received normally, with the network configured; OFF when the data is lost; turns also OFF in an abnormality in the network.
I/O-mixed units (E1, E2, R1 and S1): Functions of both input and output units are used.
[CAUTION]
When the network is reconfigured e.g. by noise interference, the RUN LED and output for all units on the network turn briefly OFF until they are turned ON after the reconfiguration is complete.

EXTERNAL VIEW

CONNECTION DIAGRAM

DIMENSIONS unit: mm (inch)

MOUNTING REQUIREMENTS unit: mm [inch]

FUNCTION BLOCK DIAGRAM

SYSTEM CONFIGURATION EXAMPLES