ES-6510 Rev.12

DLA1

Multiplex Transmission System

STANDARD MULTI-TRANSMISSION UNIT

Functions & Features
•Multiple transmission system without any software by setting station No.
•All-in-one (self-contained) hardware
•Twisted-pair cable or fiber optics
•Expansion and branching with Repeaters (model: DAL4)
•Removable terminal block
•Error detection
•Monitor LEDs provided for contact I/O units

MODEL: DLA1–[1][2]–[3][4]

ORDERING INFORMATION

• Code number: DLA1–[1][2]-[3][4]
Specify a code from below for each of [1] through [4].
  (e.g. DLA1-2A1-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)
Refer to each unit specifications.

[1] TRANSMISSION MEDIA

1: Twisted-pair cable
2: Fiber optics cable
7: Twisted-pair – fiber optics (repeater incorporated)

[2] I/O SECTION

A1: Di 32 points
A2: Di 64 points
C1: Do 32 points (relay)
C2: Do 32 points (open collector)
C3: Do 64 points (relay)
C4: Do 64 points (open collector)
E1: Di 16 + Do 16 points (relay)
E2 : Di 16 + Do 16 points (open collector)
G1x: Ai 32 points
M1x: Ao 32 points
P1x : Pi 16 + Ai 16 points
R1xx: Ai 16 + Ao 16 points
S1xx: Ai 8 + Ao 8 + Di 8 + Do 8 points
U1x : Po 16 + Ao 16 points

[3] POWER INPUT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
L: 170 – 264 V AC
(Operational voltage range 170 – 264 V, 47 – 66 Hz)
DC Power
S: 12 V DC
(Operational voltage range 12 V ±10 %, ripple 10 %p-p max.)
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[4] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Remote I/O interface unit (model: DLC)
• Telemetering unit (model: DLS)
• Repeater (model: DAL4)
• Lightning surge protector (model: MDP-DM3)
• Adapter connector (model: CND)

GENERAL SPECIFICATIONS

Construction: Surface mounting; terminal access on the front
Connection
Transmission line terminal
: Euro type connector terminal
(Applicable wire size: ≤ 1.25 mm2, stripped length 8 mm)
Power supply terminal: Euro type connector terminal
(Applicable wire size: ≤ 1.25 mm2, stripped length 8 mm)
RUN contact: Euro type connector terminal
(Applicable wire size: ≤ 1.25 mm2, stripped length 8 mm)
I/O section
32-point I/O (or less): 40-pin connector terminal; M3 × 6 screws (torque 0.7 N·m)
64-point I/O: FCN 40-pin connector (two);
OTAX N365P040AU
(FUJITSU FCN-365P040-AU...discontinued)
Housing material: Flame-resistant resin (beige)
Isolation: I/O to transmission section to power
Station No. setting: 2 rotary switches; 00 – FF (256)
Controller & Transmission Sections
Power indicator
: Red LED turns ON in normal conditions; OFF when the voltage level becomes low.
RUN indicator: Red LED turns OFF in error.
I/O Section
Contact I/O indicator LED
: Red LEDs turn on when the respective I/O channels are ON.
Analog I/O CPU RUN indicator LED: Red LED turns ON when the CPU function proves normal, OFF in error.
RUN Contact Output: Contact opens in error.
Rated load: 100 V AC or 30 V DC @ 1 A (resistive load)
Maximum switching voltage: 120 V AC or 30 V DC
Maximum switching power: 100 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Error detection
•Communication
: The receiver units detect loss of communication and wire break.
•CPU: Watch-dog timer
•Power voltage: Detects when the voltage supply to the CPU drops by 10 %.

MULTIPLEX COMMUNICATION

Communication: Half-duplex, synchronous
Transmission: Conform to RS-422, EIA
Transmission speed: 125 kbps
Protocol: SIN-NET (dedicated; data format conforms to SDLC)
Error check: CRC
Twisted-pair Cable
Cable
: CPEV-0.9 dia.
Connection: Euro Type connector terminal
(Applicable wire size: ≤ 1.25 mm2, stripped length 8 mm)
Transmission Distance: 1 kilometer max. with 16 units connected; 3 kilometers max. between 2 stations each of which consists of 3 units
Terminator: Incorporated (Remove the attached jumper pin when the unit is not located at the end of transmission line.)
Fiber Optics Cable
Link
: JIS F07 connector (Consult factory for details)
Transmission distance: 1 kilometer max. with PCF
Transmission loss: 7 dB max.
Twisted-pair – Fiber Optics: Converting signals between two media and waveform shaping

INSTALLATION

Power consumption
AC: Approx. 17.5 VA
DC: Approx. 17 W (1.1 A with 24 V)
Grounding: Not required in normal environments; 100 Ω or less grounding resistance in noisy environments
Operating temperature: -5 to + 50°C (23 to 122°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Surface; Rack Mounting Frame (model: BX-1DL) available
Weight: 2 kg (4.4 lb)

PERFORMANCE

Permissible power failure duration
AC: ≤ 20 ms
DC: ≤ 1 ms
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(I/O to transmission to power to
ground)

DESCRIPTIONS

RUN Contact (LED) Behaviors
Input units
Input units (A1, A2, G1 and P1)
: The LED turns ON with the network built-up; OFF in error; the network is reconfigured after an error.
Connecting the input unit to the DLC
The LED remains ON regardless of the input command of the DLC.
Output units
Output units (C1, C2, C3, C4, M1 and U1): The LED turns ON when data from the paired input unit is received normally, with the network configured; OFF when the data is lost; turns also OFF in error in the network.
Transmission via the DLS units: The LED remains ON regardless of the input unit status or telecomm. line status, once it is turned ON.
Connecting the output unit to the DLC
After the output unit receives the output command from the DLC, the LED turns ON and remains ON regardless of the data update.
I/O-mixed units (E1, E2, R1 and S1): The LED turns ON when data from the paired input unit is received normally, with the network configured; OFF in case of data loss or network error.
Connecting the I/O-mixed unit to the DLC
After the I/O unit receives the output command from the DLC regardless whether input or output, the LED turns ON and remains ON regardless of the data update.
[CAUTION]
When the network is reconfigured e.g. by noise interference, the RUN LED and output for all units on the network turn briefly OFF until they are turned ON after the reconfiguration is complete.
Station Number (Address)
A) 1 input unit and X output units
: Match the address for input and output units. The input data can be output at several units. A 64-point input unit needs two station numbers. Do not assign the number following the one set for a 64-point input unit to another unit.
B) 64-point contact input unit to 32-point output units: Match the number for input and one output units, then set a consecutive number for the other output unit.
[example]
input unit → 01
output unit → 01 & 02
C) 32-point contact input units to 64-point output unit: Match the number for the output and one input units, then set a consecutive number for the other input unit.
[example]
input unit → 01 & 02
output unit → 01
D) I/O mixed units: Set an even number and a consecutive number for the 2 corresponding units.
[example] 02 & 03
A combination of 3 units or more is not allowed.
E) Computer interface: Set address numbers to correspond with the computer as I/O unit.
Transmission Time
Integrate all the transmission time for each process input unit in the system.
•Contact input 32 points (A1): 1.5 msec.
•Contact input 64 points (A2): 3.0 msec.
•Contact I/O each 16 points (E1): 1.5 msec.
•Analog input 32 points (G1): 48.0 msec.
•Analog/pulse Input each 16 points (P1): 48.0 msec.
•Analog I/O each 16 points (R1): 24.0 msec.
•Analog & contact I/O each 8 points (S1): 12.0 msec.
An analog unit does not transmit all its points in serial but does 1 point per each cycle. For example, when 1 contact input unit and 1 analog input unit (32 points for each) are connected, 32 point contact signal and 1 point analog signal are transmitted in turn. One cycle time is therefore calculated as:
32 times × 1.5 msec. + 48 msec. = 96 msec.
This method is beneficial for giving a priority to contact signals which vary rapidly.

EXTERNAL VIEW

CONNECTION DIAGRAM

EXTERNAL DIMENSIONS unit: mm [inch]

MOUNTING REQUIREMENTS unit: mm [inch]

FUNCTION BLOCK DIAGRAM