ES-2736 Rev.10
ALAC
Limit Alarms (rotary switch adj.) AL-UNIT
AC ALARM
Functions & Features
• Providing SPDT relay outputs at preset AC current/voltage levels
• True RMS sensing
• Dual (Hi/Lo) trip
• Energized or de-energized coil at a tripped
condition selectable
• Rotary switch setpoint adjustments
• Enclosed relays
• Relays can be powered 110 V DC
• High-density mounting
Typical Applications
• Annunciator
• Various alarm applications
MODEL: ALAC-[1][2][3]-[4][5]
ORDERING INFORMATION
• Code number: ALAC-[1][2][3]-[4][5]
Specify a code from below for each of [1] through [5].
(e.g. ALAC-AA11-B/Q)
• Special input range (For codes AZ & A8)
• Specify the specification for option code /Q
(e.g. /C01/S01)
[1] INPUT
Current
AA
: 0 – 10 mA AC (Input resistance 100 Ω)
AB
: 0 – 50 mA AC (Input resistance 20 Ω)
AC
: 0 – 100 mA AC (Input resistance 10 Ω)
AD
: 0 – 500 mA AC (Input resistance 1 Ω)
AZ
: Specify current (See INPUT SPECIFICATIONS)
(0 % input must be 0 mA.)
Voltage
A1
: 0 – 100 mV AC (Input resistance 100 kΩ min.)
A2
: 0 – 500 mV AC (Input resistance 100 kΩ min.)
A3
: 0 – 1 V AC (Input resistance 100 kΩ min.)
A4
: 0 – 5 V AC (Input resistance 100 kΩ min.)
A5
: 0 – 10 V AC (Input resistance 100 kΩ min.)
A6
: 0 – 120 V AC (Input resistance 100 kΩ min.)
A7
: 0 – 150 V AC (Input resistance 100 kΩ min.)
A8
: Specify voltage (See INPUT SPECIFICATIONS)
(0 % input must be 0 V.)
[2] SETPOINT 1 OUTPUT
1
: Hi (coil energized at alarm)
2
: Hi (coil de-energized at alarm)
3
: Lo (coil energized at alarm)
4
: Lo (coil de-energized at alarm)
[3] SETPOINT 2 OUTPUT
1
: Hi (coil energized at alarm)
2
: Hi (coil de-energized at alarm)
3
: Lo (coil energized at alarm)
4
: Lo (coil de-energized at alarm)
[4] POWER INPUT
AC Power
B
: 100 V AC
C
: 110 V AC
D
: 115 V AC
F
: 120 V AC
G
: 200 V AC
H
: 220 V AC
J
: 240 V AC
DC Power
S
: 12 V DC
R
: 24 V DC
V
: 48 V DC
P
: 110 V DC
[5] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: Input to output 1 to output 2 to power
Input waveform
: Up to 15 % of 3rd harmonic content
Setpoint adjustments:
10-position rotary switches (front); 0 – 99 % independently; 1 % increments
Hysteresis (deadband):
0.7 – 2.5 %
Front LEDs
: Red LED turns on when the coil is energized.
Power ON timer
: Relays de-energized for approx. 2 seconds after power is turned on.
INPUT SPECIFICATIONS
Frequency
: 40 Hz min., 1 kHz max.
■
AC Current
: 0 – 1 A AC; input resistor incorporated
Minimum span
: 1 mA
Input resistance
Span 1 mA: 1 kΩ
Span ≤ 2 mA: 500 Ω
Span ≤ 5 mA: 200 Ω
Span ≤ 10 mA: 100 Ω
Span ≤ 20 mA: 50 Ω
Span ≤ 50 mA: 20 Ω
Span ≤ 100 mA: 10 Ω
Span ≤ 500 mA: 1 Ω
Span ≤ 1 A: 0.5 Ω
■
AC Voltage
: 0 – 250 V AC
Minimum span
: 50 mV
Input resistance
: 100 kΩ min.
OUTPUT SPECIFICATIONS
■
Relay Contact
: 100 V AC @ 1 A (cos ø = 1)
120 V AC @ 1 A (cos ø = 1)
240 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 1 A (resistive load)
Maximum switching voltage
: 380 V AC or 125 V DC
Maximum switching power
: 120 VA or 30 W
Minimum load
: 5 V DC @ 10 mA
Mechanical life
: 5 x 10
7
cycles
For maximum relay life with inductive loads, external protection is recommended.
INSTALLATION
Power input
•
AC
: Operational voltage range: rating ±10 %,
50/60 ±2 Hz, approx. 2 VA
•
DC
: Operational voltage range: rating ±10 %, or 85 – 150 V for 110 V rating (ripple 10 % p-p max.)
approx. 2 W (80 mA at 24 V)
Operating temperature
: -5 to +60°C (23 to 140°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Surface or DIN rail
Weight
: 370 g (0.82 lb)
PERFORMANCE in percentage of span
Setpoint accuracy
: ±0.9 %
Trip point repeatability
: ±0.05 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: Approx. 0.7 sec. (0 – 100 % at 90 % setpoint)
Line voltage effect
: ±0.1 % over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @1 minute (input to output 1 to output 2 to power to ground)
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM