ES-4211 Rev.9
6TS1
Field-mounted Two-wire Signal Conditioners 6-UNIT
THERMOCOUPLE TRANSMITTER
(field-configurable; non-linearization)
Functions & Features
• Accepting direct input from a thermocouple and providing a standard 4 – 20 mA DC signal
• Field selectable temperature range
• Burnout protection
• High-accuracy cold junction compensation
• Rugged enclosure
Typical Applications
• High-accuracy cold junction compensation benefits narrow span measurements
• 0.1 μA burnout sensing enables long distance transmission with minimum offset drifts
• Electric furnace (isolation)
MODEL: 6TS1–[1][2]
ORDERING INFORMATION
• Code number: 6TS1-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. 6TS1-2/BL)
• Temperature range (e.g. 0 – 800°C)
• Mounting adapter (e.g. surface mounting adapter plate, model: A-01)
Note: When a mounting adapter is required, specify mounting adapter. Not included without specifying.
[1] INPUT THERMOCOUPLE
1
: (PR) (Usable Range 0 to 1760°C, 32 to 3200°F)
2
: K (CA) (Usable range -270 to +1370°C, -454 to +2498°F)
3
: E (CRC) (Usable range -270 to +1000°C, -454 to +1832°F)
4
: J (IC) (Usable range -210 to +1200°C, -346 to +2192°F)
5
: T (CC) (Usable range -270 to +400°C, -454 to +752°F)
6
: B (RH) (Usable range 0 to 1820°C, 32 to 3308°F)
7
: R (Usable range -50 to +1760°C, -58 to +3200°F)
8
: S (Usable range -50 to +1760°C, -58 to +3200°F)
0
: Specify
[2] OPTIONS
Burnout
blank
: Upscale burnout
/BL
: Downscale burnout
RELATED PRODUCTS
• Outdoor enclosure (model: 6BX-E)
PACKAGE INCLUDES...
• Mounting adapter
surface mounting adapter plate (model: A-01)
Spring clip (model: A-02)
DIN rail mounting plate (model: A-31)
Note: When a mounting adapter is required, specify mounting adapter. Not included without specifying.
When using in combination with outdoor enclosure (model: 6BX-E), use a spring clip (model: A-02).
GENERAL SPECIFICATIONS
Connection
: M3 screw terminals (torque 0.6 N·m)
Screw terminal
: Nickel-plated steel
Housing material
: Diecast aluminum
Isolation
: Input to output
Output limit
: Approx. 120 %
Zero adjustment
: -3 – +15 % (behind the access cover)
Span adjustment
: 90 to 110 % (behind the access cover)
DIP/rotary switches
: For input calibration
(Refer to the instruction manual)
Linearization
: Not provided
Cold junction compensation
: CJC sensor attached to the
input terminals
INPUT SPECIFICATIONS
Minimum span
: 3 mV
Offset
: Max. 1.5 times span
Input resistance
: 20 kΩ minimum
Burnout sensing
: 0.1 μA
Minimum temperature span
(in °C)
(PR): min. span 370°C
K (CA): min. span 75°C
E (CRC): min. span 50°C
J (IC): min. span 60°C
T (CC): min. span 75°C
B (RH): min. span 780°C
R: min. span 360°C
S: min. span 380°C
Minimum temperature span
(in °F)
(PR): min. span 670°F
K (CA): min. span 140°F
E (CRC): min. span 90°F
J (IC): min. span 110°F
T (CC): min. span 140°F
B (RH): min. span 1410°F
R: min. span 650°F
S: min. span 690°F
Note: For the temperatures that range below 0°C, the transmitter may partially not satisfy the described accuracy. Consult factory.
OUTPUT SPECIFICATIONS
Output
: 4 – 20 mA DC
Load resistance vs. supply voltage
: Load Resistance (Ω) = (Supply Voltage (V) – 13 (V)) ÷ 0.02 (A)
(including leadwire resistance)
INSTALLATION
Supply voltage
: 13 – 28 V DC
Operating temperature
: -5 to +70°C (23 to 158°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail with mounting plate A-31; surface mounting with adapter plate A-01; spring clip A-02 for 3-inch hub
Weight
: 220 g (0.49 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Cold junction compensation error
(at 25°C ±10°C or 77°F ±18°F)
K, E, J & T
: ±0.5°C or ±0.9°F
S, R & PR
: ±1°C or ±1.8°F
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
±0.02 %/°C (±0.01 %/°F) at spans ≤ 10 mV
Response time
: ≤ 0.5 sec. (0 – 90 %)
Burnout response
: ≤ 10 sec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute
(input to output)
1500 V AC @ 1 minute
(input or output to ground)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM