ES-4219 Rev.11
6SN
Field-mounted Two-wire Signal Conditioners 6-UNIT
INPUT LOOP POWERED ISOLATOR
Functions & Features
• Loop-powered design eliminates output loop power supply
• 500 V DC input-to-output isolation
• 350 Ω output drive with 4 – 20 mA
• Rugged enclosure
Typical Applications
• Isolation between control room and field instrumentation, between telemetering system and input device
• Eliminates ground problems in existing systems thanks to easiness of application without requiring additional power wiring
MODEL: 6SN–[1]
ORDERING INFORMATION
• Code number: 6SN-[1]
Specify a code from below for [1].
(e.g. 6SN-A)
• Mounting adapter (e.g. surface mounting adapter plate, model: A-01)
Note: When a mounting adapter is required, specify mounting adapter. Not included without specifying.
[1] INPUT
A
: 4 – 20 mA DC
H
: 10 – 50 mA DC
RELATED PRODUCTS
• Outdoor enclosure (model: 6BX-E)
PACKAGE INCLUDES...
• Mounting adapter
surface mounting adapter plate (model: A-01)
Spring clip (model: A-02)
DIN rail mounting plate (model: A-31)
Note: When a mounting adapter is required, specify mounting adapter. Not included without specifying.
When using in combination with outdoor enclosure (model: 6BX-E), use a spring clip (model: A-02).
GENERAL SPECIFICATIONS
Connection
: M3 screw terminals (torque 0.6 N·m)
Screw terminal
: Nickel-plated steel
Housing material
: Diecast aluminum
Isolation
: Input to output
Zero adjustment
: -0.5 to +0.5 % (behind the access cover)
Span adjustment
: 98.5 to 101.5 % (behind the access cover)
INPUT & OUTPUT
■
Input 4 – 20 mA DC / Output 4 – 20 mA DC
Equivalent input impedance
: 230 Ω + load resistance with 20 mA input
Operational range
: 3 – 22 mA DC
(Accuracy is assured within 4 – 22 mA)
Load resistance
: 350 Ω maximum; min. 50 Ω required for adequate operation
■
Input 10 – 50 mA DC / Output 4 – 20 mA DC
Equivalent input impedance
: 90 Ω + [load resistance x 0.16] with 50 mA input
Operational range
: 7 – 55 mA DC
(Accuracy is assured within 8 – 55 mA)
Load resistance
: 600 Ω maximum; min. 50 Ω required for adequate operation
•INPUT 4 – 20mA DC / OUTPUT 4 – 20 mA DC
•INPUT 10 – 50 mA DC / OUTPUT 4 – 20 mA DC
INSTALLATION
Operating temperature
: -5 to +70°C (23 to 158°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail with mounting plate A-31; surface mounting with adapter plate A-01; spring clip A-02 for 3-inch hub
Weight
: 220 g (0.49 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.1 %
Temp. coefficient
: ±0.02 %/°C (±0.01 %/°F)
Response time
4 - 20 mA DC input
: Approx. 45 msec. (0 – 90 %, 50 Ω load)
10 - 50 mA DC input
: Approx. 15 msec. (0 – 90 %, 50 Ω
load)
Load effect
(The unit is calibrated with 250 Ω load at the factory.)
•
4 – 20 mA input
:
0.015 %/Ω (50 – 150 Ω)
0.003 %/Ω (150 – 350 Ω)
•
10 – 50 mA input
:
0.015 %/Ω (50 – 100 Ω)
0.003 %/Ω (100 – 600 Ω)
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute
(input to output)
1500 V AC @ 1 minute
(input or output to ground)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]