ES-4233 Rev.10
6PA
Field-mounted Two-wire Signal Conditioners 6-UNIT
FREQUENCY TRANSMITTER
(field-selectable freq. range)
Functions & Features
• Converting the output from a pulse-type transducer into a standard 4 – 20 mA DC signal
• Field selectable frequency range
• Rugged enclosure
Typical Applications
• Positive displacement flowmeters, turbine flowmeters and vortex flowmeters
• Proximity switches
• Oval flowmeters
MODEL: 6PA-2
ORDERING INFORMATION
• Code number: 6PA-2
• Frequency range (e.g. 0 – 500 Hz)
User’s frequency range specified when ordering determines the field adjustable range of the 6PA. Refer to the table below and check the range before ordering.
ORDER SPECIFIED FREQ: ADJUSTABLE RANGE
36 Hz – 100 Hz: 36 Hz – 120 Hz
100 Hz – 240 Hz: 90 Hz – 300 Hz
240 Hz – 480 Hz: 180 Hz – 600 Hz
480 Hz – 1.0 kHz: 360 Hz – 1.2 kHz
1.0 kHz – 2.4 kHz: 0.9 kHz – 3.0 kHz
2.4 kHz – 4.8 kHz: 1.8 kHz – 6.0 kHz
4.8 kHz – 12 kHz: 3.6 kHz – 12 kHz
• Mounting adapter (e.g. surface mounting adapter plate, model: A-01)
Note: When a mounting adapter is required, specify mounting adapter. Not included without specifying.
INPUT
2
: Voltage pulse
RELATED PRODUCTS
• Outdoor enclosure (model: 6BX-E)
PACKAGE INCLUDES...
• Mounting adapter
surface mounting adapter plate (model: A-01)
Spring clip (model: A-02)
DIN rail mounting plate (model: A-31)
Note: When a mounting adapter is required, specify mounting adapter. Not included without specifying.
When using in combination with outdoor enclosure (model: 6BX-E), use a spring clip (model: A-02).
GENERAL SPECIFICATIONS
Connection
: M3 screw terminals (torque 0.6 N·m)
Screw terminal
: Nickel-plated steel
Housing material
: Diecast aluminum
Zero adjustment
: -5 to +5 % (behind the access cover)
Span adjustment
: 95 to 105 % (behind the access cover)
Rotary switch
: For input calibration
(Refer to the instruction manual)
INPUT SPECIFICATIONS
■
Voltage Pulse
:
Frequency range
: 0 – 36 Hz through 12 kHz
Input amplitude
:
100 mVp-p – 50 Vp-p (≤ 1.2 kHz range)
200 mVp-p – 50 Vp-p (≥ 0.9 kHz range)
Pulse width requirement
: Duty ratio 20 – 80 %
Input impedance
: 100 kΩ
OUTPUT SPECIFICATIONS
Output
: 4 – 20 mA DC
Load resistance vs. supply voltage
: Load Resistance (Ω) = (Supply Voltage (V) – 13 (V)) ÷ 0.02 (A)
(including leadwire resistance)
INSTALLATION
Supply voltage
: 13 – 28 V DC
Operating temperature
: -5 to +70°C (23 to 158°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: DIN rail with mounting plate A-31; surface mounting with adapter plate A-01; spring clip A-02 for 3-inch hub
Weight
: 220 g (0.49 lb)
PERFORMANCE in percentage of span
Accuracy
: ±0.2 % (±0.5 % at spans ≤ 600 Hz)
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Response time
: Approx. 4 sec. (0 – 90 %)
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM