ES-6637 Rev.3
61S
Field Network Modules 61-UNIT Series
ANALOG I/O MODULE
(Multiplex Transmission System)
Functions & Features
• Interfacing analog I/O signals from/to Mini-M or Pico-M modules with Multiplex Transmission System
• Saving power and I/O wiring inside an instrumentation panel
MODEL: 61S–16[1]–[2][3]
ORDERING INFORMATION
• Code number: 61S-16[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. 61S-161-K/Q)
• Specify the specification for option code /Q
(e.g. /C01)
NO. OF CHANNELS
16
: 16 points
[1] I/O TYPE
1
: Input
2
: Output
[2] POWER INPUT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
(Specify power suffix code R (24 V DC) when the UNIT is to be
combined with the M8BS2.)
[3] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
RELATED PRODUCTS
• Installation Base (model: M2BS2)
• Installation Base (model: M8BS2)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
SIN-NET,
RUN contact output
: Euro type connector
terminal (applicable wire size: 0.2 to 2.5 mm
2
,
stripped length 7 mm)
I/O
: Via Installation Base (model: MxBS2)
Power input
: Via Installation Base (model: MxBS2)
Housing material
: Flame-resistant resin (black)
Isolation
: I/O to SIN-NET to RUN contact output to power
Power indicator
: Red LED turns ON in normal conditions; OFF when the voltage level becomes low.
RUN indicator
: Red LED turns ON when the selfdiagnosis proves normal, OFF in an abnormality.
■
RUN Contact Output
: Contact opens at error
Rated load
: 30 V DC @ 0.4 A (resistive load)
Maximum switching voltage
: 125 V DC
Maximum switching power
: 60 W
Minimum load
: 10 mV DC @ 1 mA
Mechanical life
: 5 x 10
7
cycles
Self-diagnosis
Communication
: The receiver modules detect loss of communication and wire break.
CPU
: Watch-dog timer
Memory
: Sum check
Power voltage
: Detects when the voltage supply to the CPU drops.
COMMUNICATION
Configuration
: Multi-drop
Standard
: Conforms to EIA RS-422
Communication
: 2-wire, half-duplex
Transmission speed
: 125 kbps
Control procedure
: SDLC
Data encoding
: NRZ
Protocol
: SIN-NET (dedicated protocol)
Error check
: CRC
Transmission distance
: 500 m
Transmission media
: Twisted-pair cable CPEV-0.9 dia.
Station No.
: Rotary switch
Terminator
: Incorporated (remove jumper pin with those modules not located at the end of transmission line)
INPUT SPECIFICATIONS
■
Analog Input
Input range
: 1 – 5 V DC
Input resistance
: ≥ 1 MΩ
(Each input must be isolated by signal conditioners. Non-isolated modules such as M2BW and M8BW are not usable.)
A / D conversion
Moving averaging
: 4 samples
Sampling rate
: 160 ms
OUTPUT SPECIFICATIONS
■
Analog Output
Output range
: 1 – 5 V DC
Load resistance
: 20 kΩ minimum
(Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held. Non-isolated modules such as M2BW and M8BW are not usable. )
INSTALLATION
Power consumption
•
AC
: Approx. 4 VA
•
DC
: Approx. 4 W (160 mA)
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Installation Base (model: MxBS2)
Weight
: 250 g (0.55 lb)
PERFORMANCE in percentage of span
A/D conversion
: ±0.1 %
D/A conversion
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration
: ≤ 10 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (I/O to SIN-NET to RUN contact output to power)
DESCRIPTIONS
■
RUN Contact Output (LED) Behaviors
•
Input module
The LED for the Input Modules turns ON when the network is on-line.
When there is an abnormality in the network, the LED turns OFF.
The network is reconfigured after an abnormality.
•
Output module
The LED for the Output Modules turns ON when the network is on-line and the module receives data from the corresponding Input Module.
When there is an abnormality in the network or there is no data receiving, the LED turns OFF.
■
Station Number (Address)
A)
1 input module and X output modules
:
Match the address for input and output modules.
B)
Computer interface
:
Set address numbers to correspond with the computer as output module.
■
Transmission Time
Integrate all the transmission time for each process input module in the system.
• Analog input 16 points: 24 msec.
An analog module does not transmit all its signals in serial but does 1 point per each cycle. For example, when 1 contact input module (DLA1, 32 points) and 1 analog input module (16 points) are connected, 32-point contact signal and 1 point analog signal are transmitted in turn.
One cycle time is therefore calculated as:
32 points x 1.5 msec. + 24 msec. = 72 msec.
This method is beneficial for giving a priority to contact signals which vary rapidly.
■
Applicable models for use with 61S Input Module
• 61S-162 (Ao 16 points)
• DLA1-xM1 (Ao 32 points; only the top 16 out of 32 are used)
EXTERNAL VIEW
EXTERNAL DIMENSIONS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM