ES-6612 Rev.4
60S
Field Network Modules 60-UNIT Series
ANALOG I/O MODULE
(Multiplex Transmission System)
Functions & Features
• Interfacing analog I/O signals from/to 10-RACK or 18-RACK modules with Multiplex Transmission System
• Saving power and I/O wiring inside an instrumentation panel
MODEL: 60S-16[1]-[2][3]
ORDERING INFORMATION
• Code number: 60S-16[1]-[2][3]
Specify a code from below for each of [1] through [3].
(e.g. 60S-161-K/Q)
• Specify the specification for option code /Q
(e.g. /C01/S01)
NO. OF CHANNELS
16
: 16 points
[1] I/O TYPE
1
: Input
2
: Output
[2] POWER INPUT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 66 Hz)
DC Power
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank
: none
/Q
: With options (specify the specification)
SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to our web site.)
/C01
: Silicone coating
/C02
: Polyurethane coating
/C03
: Rubber coating
TERMINAL SCREW MATERIAL
/S01
: Stainless steel
RELATED PRODUCTS
•Special cable (model: MCN34)
GENERAL SPECIFICATIONS
Construction
: Plug-in
Connection
SIN-NET,
RUN contact output
: Euro type connector
terminal (applicable wire size: 0.2 to 2.5 mm
2
, stripped
length 7 mm)
I/O
: 34-pin connector (OMRON XG4A-3434)
Power input
: M3.5 screw terminals
Screw terminal
: Chromated steel (standard) or stainless steel
Housing material
: Flame-resistant resin (black)
Isolation
: I/O to SIN-NET to RUN contact output to power to FG1
Power indicator
: Red LED turns ON in normal conditions; OFF when the voltage level becomes low.
RUN indicator
: Red LED turns ON when the selfdiagnosis proves normal, OFF in an abnormality.
■
RUN Contact Output
: Contact opens at error
Rated load
: 30 V DC @ 0.4 A (resistive load)
Maximum switching voltage
: 125 V DC
Maximum switching power
: 60 W
Minimum load
: 10 mV DC @ 1 mA
Mechanical life
: 5 x 10
7
cycles
Self-diagnosis
Communication
: The receiver modules detect loss of communication and wire break.
CPU
: Watch-dog timer
Memory
: Sum check
Power voltage
: Detects when the voltage supply to the CPU drops.
COMMUNICATION
Configuration
: Multi-drop
Standard
: Conforms to EIA RS-422
Communication
: 2-wire, half-duplex
Transmission speed
: 125 kbps
Control procedure
: SDLC
Data encoding
: NRZ
Protocol
: SIN-NET (dedicated protocol)
Error check
: CRC
Transmission distance
: 500 m
Transmission media
: Twisted-pair cable CPEV-0.9 dia.
Station No.
: Rotary switch
Terminator
: Incorporated (remove jumper pin with those modules not located at the end of transmission line)
INPUT SPECIFICATIONS
■
Analog Input
Input range
: 1 – 5 V DC
Input resistance
: ≥ 1 MΩ
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
OUTPUT SPECIFICATIONS
■
Analog Output
Output must be isolated with signal conditioners.
When the transmission line is open, the last value sampled before failure is held.
Output range
: 1 – 5 V DC
Load resistance
: 20 kΩ minimum
10-RACK and 18-RACK I/O modules must be isolated types. Non-isolated modules such as 10BW and 18BW are not usable.
INSTALLATION
Power consumption
•
AC
: Approx. 4 VA
•
DC
: Approx. 4 W (160 mA)
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Atmosphere
: No corrosive gas or heavy dust
Mounting
: Surface or DIN rail
Weight
: 450 g (0.99 lb)
PERFORMANCE in percentage of span
A/D conversion
: ±0.1 %
D/A conversion
: ±0.1 %
Temp. coefficient
: ±0.015 %/°C (±0.008 %/°F)
Permissible power failure duration
: ≤ 10 msec.
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1500 V AC @ 1 minute (input or output to SIN-NET to RUN contact output to power)
2000 V AC @ 1 minute (input or output or SIN-NET or RUN contact output or power to FG1)
DESCRIPTIONS
■
RUN Contact Output (LED) Behaviors
•
Input module
The LED for the Input Modules turns ON when the network is on-line.
When there is an abnormality in the network, the LED turns OFF.
The network is reconfigured after an abnormality.
•
Output module
The LED for the Output Modules turns ON when the network is on-line and the module receives data from the corresponding Input Module.
When there is an abnormality in the network or there is no data receiving, the LED turns OFF.
■
Station Number (Address)
A)
1 input module and X output modules
:
Match the address for input and output modules.
B)
Computer interface
:
Set address numbers to correspond with the computer as output module.
■
Transmission Time
Integrate all the transmission time for each process input module in the system.
•Analog input 16 points: 24.0 msec.
An analog module does not transmit all its signals in serial but does 1 point per each cycle. For example, when 1 contact input module (DLA1, 32 points) and 1 analog input module (16 points) are connected, 32 point contact signal and 1 point analog signal are transmitted in turn. One cycle time is therefore calculated as:
32 points × 1.5 msec. + 24 msec. = 72 msec.
This method is beneficial for giving a priority to contact signals which vary rapidly.
■
Applicable models for use with 60S Input Module
• 60S-162 (Ao 16 points)
• DLA1-xM1 (Ao 32 points; only the top 16 out of 32 are used)
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM