ES-9430 Rev.1
43EDY
Digital Panel Meters 43E Series
CURRENT LOOP SUPPLY DIGITAL PANEL METER
(sensor excitation, alarm output)
Functions & Features
• -1999 to +9999 digital panel meter
• Screwless spring terminal
• External power supply incorporated
• Linearization and Square root extraction are switchable
• 2 points alarm
MODEL: 43EDY–[1]-[2][3]
ORDERING INFORMATION
• Code number: 43EDY-[1]-[2][3]
Specify a code from below for each of [1] and [3].
(e.g. 43EDY-1-R/Q)
• Specify the specification for option code /Q
(e.g. /SET)
INPUT
Current
4 – 20 mA DC (Input resistance 10 Ω)
[1] ALARM OUTPUT
1
: N.O. relay contact, 2 points
2:
Photo MOSFET relay, N.O., 2 points
[2] POWER INPUT
DC Power
T
: 5 V DC
(Operational voltage range 5 V ± 5 %, ripple 10 %p-p max.)
R
: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
[3] OPTIONS
blank
: none
/Q
: Options other than the above (specify the specification)
SPECIFICATIONS OF OPTION: Q
EX-FACTORY SETTING
/SET
: Preset according to the Ordering Information Sheet
(No. ESU-9430)
GENERAL SPECIFICATIONS
Construction
: Panel flush mounting
Connection
: Screwless spring terminal
Applicable wire size
: 1.0 to 1.3 mm
2
, stripped length 8 mm
Housing material
: Flame-resistant resin (gray)
Isolation
: Input to alarm output to power
A/D conversion
: Σ – Δ
Sampling rate
: 5 times/sec. (200 msec.)
Averaging
: None or moving average
Setting
: (Front button)
• Scaled range
• Linearization, square root extraction
• Moving average
• Low-end cutout
• Brightness
• Others
DISPLAY
Display
: 4 digits of 7.6 mm (.3”) height, 7-segment, red LED
Display range
: -1999 to 9999
Scaling range for measurement range (c
onformance range
)
: -1999 to 9999
Decimal point position
: 10
-1
, 10
-2
, 10
-3
or none
Zero indication
: Higher-digit zeros are suppressed.
Over-range indication
: '-1999' or '9999' blinking for display values out of the display range. 'S.ERR' blinks surpassing the permissible range.
Alarm status indication
L1 indicator
: Green turns on when the L1 alarm is tripped.
L2 indicator
: Red turns on when the L2 alarm is tripped.
Engineering unit indication
: Sticker label attached
DC, AC, mV, V, kV, μA, mA, A, kA, mW, W,
kW, var, kvar, Mvar, VA, Hz, Ω, kΩ, MΩ,
cm, mm, m, m/sec, mm/min, cm/min, m/min,
m/h, m/s
2
, inch, ℓ, ℓ/s, ℓ/min, ℓ/h, m
3
, m
3
/sec,
m
3
/min, m
3
/h, Nm
3
/h, N·m, N/m
2
, g, kg, kg/h,
N, kN, Pa, kPa, MPa, t, t/h, ℃, °F, %RH, J,
kJ, MJ, rpm, sec, min, pH, %, ppm, etc.
EXCITATION SUPPLY
■
+24V SENSOR EXCITATION
Output voltage (across the terminals 3 – 1)
:
24 V DC @ 20 mA DC
•
Shortcircuit Protection
Current limited
: 40 mA maximum
Protected time duration
: No limit
INPUT SPECIFICATIONS
■ DC CURRENTINPUT
· 4 to 20 mA DC (conformance range)
Input range: 2.4 to 21.6 mA
Input resistance: approx. 10 Ω
Connect terminal 3 to 1
OUTPUT SPECIFICATIONS
■
Alarm Output
· Relay contact
Rated load
: 30 V AC 0.5 A (cosφ = 1)
30 V DC 1A (resistive load)
Minimum load
: 10 mV DC 10 μA
Mechanical life
: ≥ 5 × 10
7
cycles
For maximum relay life with inductive loads, external protection is recommended.
■
Alarm output
· Photo MOSFET relay
Rating
: 30 V DC 100 mA (resistive load)
ON resistance:
≤ 0.25 Ω
Permissible
: 250 mW
LINEARIZATION
■
Linearization Types
Linear
: The output is proportional to the input.
Square root
: The input is square root extracted.
■ Low-end Cutout
Set low-end cutout value from 0 to 99.9 % of input singal.
Outputs 0% when under low-end cutout value.
INSTALLATION
Power consumption
: 2 W max.
Power supply T: ≤ 380mA @ 5 V DC
R: ≤ 80 mA @ 24 V DC
Operating temperature
: 0 to 55°C (32 to 131°F)
Operating humidity
: 20 to 90 % RH (non-condensing)
Mounting
: Panel flush mounting
Weight
: 60 g (2.12 oz)
PERFORMANCE
Accuracy
: ±0.1 % rdg ±1 digit× scaling-multiple
(Input within 1 - 100 % for square root extraction)
Temp. coefficient
: ±(0.01%rdg + 0.3 digits) × scaling-multiple/℃
(When the scaling-multiple is less than 1, rounded up to 1.)
Scaling-multiple = | (Display Scaling Value B - Display Scaling Value A) ÷ (default Display Scaling Value B - default Display Scaling Value A) |
Response time
: ≤ 500 msec.
Line voltage effect
: ±1 digit over voltage range
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 1000 V AC @ 1 minute (input to alarm output to power to ground)
STANDARDS & APPROVALS
EU conformity
:
EMC Directive
EN 61326-1
RoHS Directive
EXTERNAL VIEW
EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm [inch]
MOUNTING REQUIREMENTS unit: mm
MOUNTING
SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM