ES-1869 Rev.9

18PA

Rack-mounted DCS Signal Conditioners 18-RACK

PHASE ANGLE TRANSDUCER

Functions & Features
• Providing two DC output signals in proportion to phase angle
• DC output containing little ripple is ideal for computer input
Typical Applications
• Centralized monitoring and control of power management system in a manufacturing facility or building
• Measuring phase angle for a motor
 

MODEL: 18PA–1[1][2]66–R

ORDERING INFORMATION

• Code number: 18PA-1[1][2]66-R
Specify a code from below for each of [1] and [2].
  (e.g. 18PA-11P66-R)

CONFIGURATION

1: 3-phase / 3-wire

[1] INPUT (balanced load)

1: 110 V / 5 A AC
2: 110 V / 1 A AC
3: 220 V / 1 A AC
4: 220 V / 5 A AC

[2] OUTPUT SIGNAL POLARITY

P: Negative in lag, positive in lead
M: Negative in lead, positive in lag

OUTPUT 1

Voltage
6: 1 – 5 V DC (Load resistance 5000 Ω min.)

OUTPUT 2

Voltage
6: 1 – 5 V DC (Load resistance 5000 Ω min.)

POWER INPUT

DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

GENERAL SPECIFICATIONS

Construction: Rack-mounted; terminal access via screw terminals on the front and connector on the rear; terminal cover provided
Connection
  Input: M3.5 screw terminals (torque 0.8 N·m)
  Output 1: Connector
  Output 2: Connector
  Power input: Supplied from connector
Screw terminal: Nickel-plated steel
Isolation: Voltage input to current input to output 1 to output 2 to power
Overrange output: Approx. -10 to +120 % at 1 – 5 V
Zero adjustment: -5 to +5 % (front)
Span adjustment: 95 to 105 % (front)

INPUT SPECIFICATIONS

Frequency: 50 or 60 Hz
Current Input
Input burden
: 0.1 VA (input 1 A)
0.5 VA (input 5 A)
Operational range: 10 – 120 % of rating
Overload capacity: 1000 % of rating for 3 sec., 200 %
for 10 sec., 120 % continuous
Voltage Input
Input burden
: Approx. 0.5 VA
Operational range: 85 – 120 % of rating
Overload capacity: 150 % of rating for 10 sec., 120 % continuous
Input range:
lag 60°– 0 – lead 60°
lead 60°– 0 – lag 60°

OUTPUT SPECIFICATIONS

INSTALLATION

Current consumption: Approx. 80 mA
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Standard Rack 18BXx or 18KBXx
Weight: 200 g (0.44 lb)

PERFORMANCE in percentage of span

Accuracy: ±2 % with balanced load
Temp. coefficient: ±0.2 %/°C (±0.11 %/°F)
Response time: ≤ 1 sec. (0 – 90 %)
Ripple: 1 %p-p max. (50/60 Hz)
Line voltage effect: ±0.1 % over voltage range
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 2000 V AC @ 1 minute
(voltage input to current input to output 1 or output 2 or power)
500 V AC @ 1 minute (output 1 to output 2 to power)
2000 V AC @ 1 minute (input or output or power to ground)

CONNECTION DIAGRAM

EXTERNAL DIMENSIONS unit: mm [inch]

TERMINAL ASSIGNMENTS