ES-0493 Rev.3
18KBXH
Rack-mounted DCS Signal Conditioners 18K-RACK
STANDARD RACK
Functions & Features
• Housing for storage of Rack-mounted DCS Signal Conditioners 18K-RACK
• Integrated rack and field terminals allow for signal conditioners to be removed without touching the terminal screws, making field wiring insulation tests possible
• Signal conditioner power via the rear rack bus for all 8 modules
• Connectors are available for direct connection to DCS units of various manufacturers
• Mounting bracket position selectable
MODEL: 18KBXH–[1][2]
ORDERING INFORMATION
• Code number: 18KBXH-[1][2]
Specify a code from below for each of [1] and [2].
(e.g. 18KBXH-E1/W)
[1] CONNECTOR
0
: None
U1
: Fujitsu FCN type I/O connector
E1
: For Toshiba DCS SAMP1 card use
E3
: For Toshiba DCS SAIN1, SAI06 and SAO06 card use
(Panasonic AXM220011 used)
(DISCONTINUED; replace with code "E3A".)
E3A
: Toshiba DCS SAIN1, SAI06, SA006 card supported
(Omron XG4A-2034 used)
E4
: For Toshiba DCS SAIN1 card use
We guarantee the connecting section.
[2] OPTIONS
Mounting Bracket
blank
: Rack mounting, standard
/W
: Surface mounting
RELATED PRODUCTS
• Blank filler plate (model: P-181)
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)
GENERAL SPECIFICATIONS
Construction
: Metal plates assembly
Coating
: Colored Zn-Cr
Capacity
: 8 positions
Connection
Power input
: M4 screw terminals (torque 0.8 N·m)
Field terminal
: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
Power
: Nickel-plated brass
Field terminal
: Nickel-plated steel
Isolation
: I/O connector to field terminal to power to FG
INSTALLATION
Power supply
: Operational voltage range: 24 V DC ±10%
Ripple 10 % p-p max. @ ≥ 1.3 A
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: Rack or Surface
Weight
: 1.8 kg (4.0 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 500 V AC @ 1 minute
(I/O connector to field terminal to power)
1000 V AC @ 1 minute (I/O connector or field terminal or power to FG)
MOUNTING REQUIREMENTS unit: mm (inch)
CONNECTION DIAGRAM
DIMENSIONS unit: mm (inch)
I/O CONNECTOR PIN ASSIGNMENT