ES-1807 Rev.9

18BXCS

Rack-mounted DCS Signal Conditioners 18-RACK

STANDARD RACK

(with grounding bar)
Functions & Features
• Standard 19" rack for 18-RACK signal conditioners
• Line power supplied via the rear rack bus
• Grounding bar
• Direct interface to various DCS with the rack connector

MODEL: 18BXCS–1[1]

ORDERING INFORMATION

• Code number: 18BXCS-1[1]
Specify a code from below for [1].
  (e.g. 18BXCS-1Y3)

FUNCTION

1: Power distribution & grounding

[1] CONNECTOR

U1: Fujitsu FCN type I/O connector
Y1: Yokogawa DCS VMx / PM1 card use
Y3: Yokogawa DCS MAC2 / PAC card use
We guarantee the connecting section.

RELATED PRODUCTS

• Blank filler plate (model: P-181)
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Construction: Metal plates assembly
Coating: Colored Zn-Cr
Capacity: 16 positions
Connection
  Power input
: M4 screw terminals (torque 0.8 N·m)
  Ground: M3.5 screw terminals (torque 0.8 N·m)
  Shield: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
Power input: Nickel-plated brass
Ground: Chromated steel
Shield: Chromated steel

INSTALLATION

Power input
DC: Operating voltage range 24 V DC ±10 %, 2.5 A minimum (ripple 10 % p-p max.)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: JIS or EIA standard rack
Weight: 3 kg (6.61 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
(I/O connector to power to FG)
Dielectric strength:
500 V AC @ 1 minute (I/O connector to power)
1000 V AC @ 1 minute (I/O connector or power to FG)

MOUNTING REQUIREMENTS

CONNECTION DIAGRAM

DIMENSIONS unit: mm (inch)

I/O CONNECTOR PIN ASSIGNMENT