ES-1892 Rev.15

18BXC

Rack-mounted DCS Signal Conditioners 18-RACK

STANDARD RACK

Functions & Features
• Standard 19" rack for 18-RACK signal conditioners
• Line power access at the terminal card, supplied via the rear rack bus 
• Direct interface to various DCS with the rack side connector

MODEL: 18BXC–1[1][2]

ORDERING INFORMATION

• Code number: 18BXC-1[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. 18BXC-11/W)

FUNCTION

1: Power distribution

[1] CONNECTOR

1: Fujitsu FCN type I/O connector
2: Yokogawa VMx / PM1 card use
3: Yokogawa MAC2 / PAC card use
H1: Hitachi DCS EX connector
H2: Hitachi DCS EX-CDL cable connector
E5: Toshiba DCS VAIMX1 card use
E6: Toshiba DCS VAOPX1 card use
K1: Yamatake DCS AI connector
K2: Yamatake DCS AO connector
K5: Yamatake DCS PI connector
V1: Shimadzu DCS connector
We guarantee the connecting section.

[2] OPTIONS

Mounting Bracket
blank: Rack mounting, standard
/W: Surface mounting

RELATED PRODUCTS

• Blank filler plate (model: P-181)
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)

GENERAL SPECIFICATIONS

Construction: Metal plates assembly
Coating: Colored Zn-Cr
Capacity: 16 positions
Connection
 Power input
: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated brass

INSTALLATION

Power input
DC: Operating voltage range 24 V DC ±10 %, 2.5 A minimum (ripple 10 % p-p max.)
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: JIS or EIA standard rack or surface
Weight: 1.7 kg (3.7 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
(I/O connector to power to FG)
Dielectric strength:
500 V AC @ 1 minute (I/O connector to power)
1000 V AC @ 1 minute (I/O connector or power to FG)

MOUNTING REQUIREMENTS

CONNECTION DIAGRAM

DIMENSIONS unit: mm (inch)

I/O CONNECTOR PIN ASSIGNMENT