ES-1892 Rev.15
18BXC
Rack-mounted DCS Signal Conditioners 18-RACK
STANDARD RACK
Functions & Features
• Standard 19" rack for 18-RACK signal conditioners
• Line power access at the terminal card, supplied via the rear rack bus
• Direct interface to various DCS with the rack side connector
MODEL: 18BXC–1[1][2]
ORDERING INFORMATION
• Code number: 18BXC-1[1][2]
Specify a code from below for each of [1] and [2].
(e.g. 18BXC-11/W)
FUNCTION
1
: Power distribution
[1] CONNECTOR
1
: Fujitsu FCN type I/O connector
2
: Yokogawa VMx / PM1 card use
3
: Yokogawa MAC2 / PAC card use
H1
: Hitachi DCS EX connector
H2
: Hitachi DCS EX-CDL cable connector
E5
: Toshiba DCS VAIMX1 card use
E6
: Toshiba DCS VAOPX1 card use
K1
: Yamatake DCS AI connector
K2
: Yamatake DCS AO connector
K5
: Yamatake DCS PI connector
V1
: Shimadzu DCS connector
We guarantee the connecting section.
[2] OPTIONS
Mounting Bracket
blank
: Rack mounting, standard
/W
: Surface mounting
RELATED PRODUCTS
• Blank filler plate (model: P-181)
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)
GENERAL SPECIFICATIONS
Construction
: Metal plates assembly
Coating
: Colored Zn-Cr
Capacity
: 16 positions
Connection
Power input
: M4 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated brass
INSTALLATION
Power input
•
DC
: Operating voltage range 24 V DC ±10 %, 2.5 A minimum (ripple 10 % p-p max.)
Operating temperature
: -5 to +55°C (23 to 131°F)
Operating humidity
: 30 to 90 %RH (non-condensing)
Mounting
: JIS or EIA standard rack or surface
Weight
: 1.7 kg (3.7 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
(I/O connector to power to FG)
Dielectric strength
:
500 V AC @ 1 minute (I/O connector to power)
1000 V AC @ 1 minute (I/O connector or power to FG)
MOUNTING REQUIREMENTS
CONNECTION DIAGRAM
DIMENSIONS unit: mm (inch)
I/O CONNECTOR PIN ASSIGNMENT