ES-2906 Rev.2
17BXE
Rack-mounted Power Transducers 17-RACK
STANDARD RACK
Functions & Features
• Standard 19" rack for 17-RACK power transducers
• Output wiring formed collectively with the rack connector
• Line power supplied via the rear rack bus
• High-density mounting (16 positions)
Typical Applications
• Measuring receiving power and branch circuits in a power facility
• Measuring load currents at branch circuits intensively
• Centralized management system of a power facility by a computer.
MODEL: 17BXE–[1]-[2][3]
ORDERING INFORMATION
• Code number: 17BXE-[1]-[2][3]
Specify a code from below for each [1] through [3].
(e.g. 17BXE-U1-R/W)
[1] CONNECTOR
U1
: Fujitsu FCN type I/O connector
UT
: Output terminal block
[2] POWER SUPPLY UNIT
AC Power
K
: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
L
: 170 – 264 V AC
(Operational voltage range 170 – 264 V, 47 – 63 Hz)
DC Power
R
: 24 V DC; no power supply unit
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)
P
: 110 V DC
(Operational voltage range 85 – 150 V, ripple 10 %p-p max.)
[3] OPTIONS
Mounting Bracket
blank
: Rack mounting, standard
/W
: Surface mounting
RELATED PRODUCTS
• Connector terminal block (model: CNT)
• Special cable with 40-pin connector (model: FCN)
GENERAL SPECIFICATIONS
Construction
: Metal plates assembly
Coating
: Colored Zn-Cr
Capacity
: 16 positions
Connection
Power input
: M4 screw terminals (torque 0.8 N·m)
Output
: Connector or M3.5 screw terminals (torque 0.8 N·m)
Screw terminal
: Nickel-plated brass
Isolation
: Output to power to FG
INSTALLATION
Power consumption
•
AC
: Approx. 100 VA
•DC
: Approx. 70 W
Operating temperature
: -5 to +55°C (23 to 131°F)
0 to 50°C (32 to 122°F) for with power supply unit
Operating humidity
: 40 to 85 % RH (non-condensing)
Mounting
: JIS or EIA standard rack or surface
Weight
Power Code R
: 3.0 kg (6.6 lb)
Power Code K, L or P
: 3.5 Kg (7.7 lb)
PERFORMANCE
Insulation resistance
: ≥ 100 MΩ with 500 V DC
Dielectric strength
: 2000 V AC @ 1 minute (output to power, 500V AC with power code R, 1500 V AC with power code K)
2000 V AC @ 1 minute (power to FG)
500 V AC @ 1 minute (output to FG)
MOUNTING REQUIREMENTS unit: mm (inch)
CONNECTION DIAGRAM
DIMENSIONS unit: mm (inch)
OUTPUT CONNECTOR