ES-0896 Rev.2

10BXU

High-density Signal Conditioners 10-RACK

STANDARD RACK

(2 positions)
Functions & Features
• Standard rack for 10-RACK signal conditioners
• Line power supplied via the rear rack bus

MODEL: 10BXU–[1][2]

ORDERING INFORMATION

• Code number: 10BXU-[1][2]
Specify a code from below for each of [1] and [2].
  (e.g. 10BXU-K/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] POWER SUPPLY UNIT

AC Power
K: 85 – 132 V AC
(Operational voltage range 85 – 132 V, 47 – 63 Hz)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[2] OPTIONS

blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q

COATING (For the detail, refer to our web site.)
Power supply and signal conditioner side of the main PWB are not coated.
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

RELATED PRODUCTS

• Blank filler plate (model: P-101)

GENERAL SPECIFICATIONS

Construction: Metal plates assembly
Coating: Zn-Cr (black), alumetized steel
Capacity: 2 positions
Connection: M3.5 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Isolation: I/O to power to FG

INSTALLATION

Power input
AC: 85 – 132 V, 47 – 63 Hz, 15 VA maximum
DC: 24 V DC ±10 %, (ripple 10 % p-p max.)
Operating temperature: -5 to 55°C (23 to 131°F)
0 to 55°C (32 to 131°F) for AC power
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Angle bracket
Weight: Approx. 1 kg (2.21 lb)

PERFORMANCE

Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(I/O to power to FG)

MOUNTING REQUIREMENTS unit: mm (inch)

CONNECTION DIAGRAM

DIMENSIONS unit: mm (inch)