TR30

Paperless Recorder TR30 Series

PAPERLESS RECORDER

Functions & Features
• By using SD card, measurement data and running / stopping status of device can be recorded. 
• ‘Browsing’ function with browser.
• To use combination with R30 series I/O module.
Flexible selection and combination are available depending on required signal type and points.

MODEL: TR30-G-R[1]

ORDERING INFORMATION
• Code number: TR30-G-R[1]
 Specify a code from below for [1].
  (e.g. TR30-G-R/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

MODULE TYPE
G: High functionality

POWER INPUT
DC power
R: 24 V DC
(Operational voltage range: ±10 %; ripple 10 %p-p max.)

[1] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

FUNCTIONS & FEATURES
TR30 is used in combination with base (model: R30BS) and I/O module (Remote I/O R30 series)
TR30
Collecting of input data, recording and transmitting output data:
Collecting data from I/O module via internal bus, recording to internal memory and recording to SD card.
Connecting between remote I/O and Modbus/TCP, and collecting and recording input data of remote I/O.
Sending alarm output to output module by setting alarm level.
• Web server:
TR30 works as a web server, showing collected data to the browser of a tablet. Various setting and operation are available.
• Internal power
Internal power required for TR30 and I/O module is generated from supplied power.
I/O Module
Performing D/A conversion of data received through the internal bus into discrete outputs; A/D conversion of field analog/discrete inputs. (Refer to the specification of each R30 I/O module)
Installation base
The base for installation of modules incorporating PWB for internal power and internal bus. (Refer to the specification of installation base (model: R30BS))

RELATED PRODUCTS
•Remote I/O R30 series
• PC Configurator cable
  USB 2.0 compatible cable
  (TR30 connector: mini-B type, 5.0m max.)
• PC configurator software (model: TRGCFG)
• PC configurator software (model: R30CFG)
• Viewer software (model: TRViewer)
Software downloadable at M-System’s web site.
• SD card
A SD card is required to store data in the unit.
Use the specified model number of memory card.
Available for purchase from M-System. Consult M-System.
  - Hagiwara Solutions NSD6-004GH, NSD6-016GH

GENERAL SPECIFICATIONS
Connection
 RUN contact output, power supply
: M3 separable screw terminal (torque 0.5 N·m)
 Ethernet: RJ-45 modular jack
 Internal bus: Via the Installation Base (model: R30BS)
 Internal power: Via the Installation Base (model: R30BS)
Solderless terminal: Refer to the drawing at the end of the section.
   Recommended manufacturer: Japan Solderless Terminal MFG. Co., Ltd., Nichifu Co., Ltd. 
  (Solderless terminals with insulation sleeve do not fit.)
  Applicable wire size: 0.25 to 0.75 mm2
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (gray)
Max. number of R30 I/O modules: 16
(Max. consumption current of I/O modules: 500 mA)
Isolation: Ethernet to internal bus or internal power to RUN contact output to power supply to FE 
Calendar clock: Year (4 digits), month, date, day, hour, minute, second
Read rate: Approx. ≤ 1 msec. (Connected max. modules)
Indicator LEDs: PWR, TR30 RUN, RECORD, SD CARD, ERROR
(Refer to the insruction manual)
RUN CONTACT OUTPUT
RUN contact output: Turns on (closed) at normal operation
Rated load: 250 V AC @ 0.5 A (cos ø = 1)
30 V DC @ 0.5 A (resistive load)
(Less than 50 V AC to conform with EU Directive)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 30 W
Minimum load: 5 V DC @ 10 mA
Mechanical life: 2 × 107 cycles (rate 300 cycles/min.) When driving an inductive load, external contact protection and noise quenching recommended.

R30 CONNECTION
■ TR30 INSTALL POSITION
Install to PWR slot (most left slot) and COM slot (right next to PWR slot).

ETHERNET COMMUNICATION
Communication Standard: IEEE 802.3u
Transmission: 10BASE-T, 100BASE-TX
Baud rate: 10/100 Mbps (Auto Negotiation function)
Protocol: TCP/IP, Modbus/TCP, HTTP, FTP, SMTP, SNTP
Transmission media: 10BASE-T (STP, Category 5) 100BASE-TX (STP, Category 5e)
Max. length of fieldbus segment: 100 meters
Ethernet indicator LED: DPX, LNK
IP address: 192.168.0.1 (factory setting)

INSTALLATION
Power consumption
DC: Approx. 18 W 24 V DC (@ output current max. 500 mA)
Internal power
• Max. rated output voltage / current: 21 V DC / 500 mA
Total current consumed at the R30 I/O modules used combination with TR30 must be within above current.
Operating temperature: 0 to 50°C (32 to 122°F)
Storage temperature: -10 to +60°C (14 to +140°F)
Operating humidity: 10 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: Installation Base (model: R30BS)
Weight: 300 g (0.66 lb)

PERFORMANCE
Calendar clock: (with battery backup)
 Accuracy: Monthly deviation 2 minutes at 25°C
 Back up period: Approx. 2 years at 25°C
 Battery: Primary lithium battery (non-removable)
 (In order to prevent battery drain, battery back up is OFF at factory default. Turn it ON prior to start using.)
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(Ethernet to internal bus or internal power to RUN contact output to power supply to FE)

STANDARD COMPLIANCE
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

EXTERNAL VIEW

TERMINAL ASSIGNMENTS

EXTERNAL DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FE terminal to ground.
Caution: FE terminal is NOT a protective conductor terminal.

DATA STORING

The trend data, event data and comment data are stored into the internal memory with specified storing rate. It is available to transfer into the SD card with the timing according to the storing rate.
Event data
• Event: Transition of analog input zone, transition of pulse input zone, status change of discrete input
• Event detection interval: Same as trend data sampling rate
• Stored contents: Date/time, event
• Number of event: 3000
Comment data
• Number of characters for comment: 32
• Stored contents: Date/time, comment.
• Number of comment: 1000

COMMUNICATION
IP
DHCP client is supported. Manual setting of IP address, subnet mask, default gateway and DNS server available too.
Web server function
This unit can be a Web server, and 'Data,' 'Trend' and 'Event Log' view are available from remote location.
Compatible terminal, browser
• iPad (iOS 10.2): Safari
• Android tablet (Android 6.0): Chrome 56.0.2924.87
• Windows PC (Windows 7, 8.1, 10), Tablet (Windows 8.1,
  10): Edge, Internet Explore 11, Firefox 52.0,
  Chrome 57.0.2987.98
Modbus/TCP master
I/O expansion with remote I/O, e.g. R3 or R7 series, is
available. Measuring points in multiple location can be
handled collectively.
■ Connectable devices
• R3-NE1
• R5-NE1
• R6-NE1, R6-NE2
• R7E series
• R9EWTU
• 72EM2-M4
• GR8-EM
• DL8 series
• TR3EX
• IT series
• 73VR series
Max. number of connectable devices
  (Number of slaves)
• 12 (nodes)
Establishing nodes for number of slaves connected.
Max. I/O points
Analog input: 64 points
Discrete input: 64 points
Pulse input: 32 points
Discrete output: 64 points
Modbus/TCP slave
Remote monitor with SCADA is available. Recording start/stop, entering comment, specifying folder/file name for SD card transfer destination and setting folder name for ftp transfer destination are available with PLC.

ALARM OUTPUT
Event can trigger an alarm contact at a discrete output module.

EVENT REPORTING E-MAIL
Reporting e-mail function available at event or designated time.
Encrypted communication is supported. (SMTP over SSL).
The TR30 turns a designated Do ON after transmitting the report.
· Number of e-mail attention: 32
· Number of event report text: 32
· Number of regular report text: 1
· Channel status: AI, DI, PI, OI, DO status attachable to e-mail
· Output at transmitting failure: 1 point

FTP CLIENT

FTP SERVER
Reading and deleting files in the SD card by an FTP client is
available.
Operation verified FTP client
• Explorer
• Web browser
Internet Explorer version 11
Firefox version 52.0 or later
Chrome 57.0.2987.98
• FFFTP 1.98g

ARITHMETIC FUNCTION
Addition and subtraction, multiplication, division, square root, moving average, delay buffer, exp, common logarithm, natural logarithm, peak hold(max/min), analog accumulation, power, F value calculation, inverse logarighm and scaling are available with function input (OI).

OTHER FUNCTIONS
Configuration: Configurable with the dedicated software model: TRGCFG

SYSTEM CONFIGURATION EXAMPLES
Devices other than the TR30 in below provided by the user.

MG Co., Ltd.