·Some details are not shown. Please refer to specification sheets for all information.

73VR1100

Paperless Recording System

PAPERLESS RECORDER
(remote I/O modules)

Functions & Features
• 100 msec. storing rate for the max. of 64 points (1 station) with the R3-NE1 module
• Graphic image view helps to recognize measuring points and signal status at a glance
• Data stored in CF Cards and SD Cards
• Memory card slot accessible at the front
• Real time monitoring at the host PC via Ethernet
• Dedicated application software to view and analyze the data
• Touch panel operation
• IP 65 front panel

MODEL: 73VR1100-[1]-[2][3]

ORDERING INFORMATION
• Code number: 73VR1100-[1]-[2][3]
 Specify a code from below for each [1] through [3].
  (e.g. 73VR1100-E-M2/Q)
• Specify the specification for option code /Q
  (e.g. /C01/S01/HA)

[1] LANGUAGE
N: Japanese
E: English

[2] POWER INPUT
AC Power
M2: 100 – 240 V AC (Operational voltage range 85 – 264 V,
 47 – 66 Hz)
  (CE not available for desktop type)
DC Power
R: 24 V DC
(Operational voltage range 24 V ±10 %, ripple 10 %p-p max.)

[3] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q (multiple selections)
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating
TERMINAL SCREW MATERIAL
/S01: Stainless steel
INSTALLATION
/HA: Desktop type (with handle and feet)
(Desktop type cannot be mounted on a panel surface.
The handle and rubber feet cannot be detached.)

RELATED PRODUCTS
Please refer to data sheets for the respective models.
• PC Recorder R1M, R2M, R1MS, RZMS series
• Remote I/O R3 series
Ethernet (Modbus/TCP) Interface Module (model: R3-NE1) Modbus Interface Module (model: R3-NM1)
• Remote I/O R5 series
Ethernet (Modbus/TCP) Interface Module (model: R5-NE1) Modbus Interface Module (model: R5-NM1)
• Modbus I/O Module (model: R7M)
• Ethernet I/O Module, Modbus/TCP (model: R7E)
R7 Configurator Software (model: R7CON) To connect with R7M series, change Modbus Communication Parameters of the R7M by using R7CON and the special cable.
• Multi Power Monitor (model: 53U)
· Ethernet Tower Light (Model: IT60RE, IT40SRE, IT50SRE, IT60SRE)
Lamps and buzzer are turned on/off in combination with alarm output of 73VR1100.
• Ethernet Communication Adaptor (model: 72EM2-M4)
■ Memory card
A memory card is required to store data in the 73VR1100. Available for purchase from M-System. Consult M-System (except SD/CF conversion adapter).
M-System will not guarantee the product’s described performance if a memory card other than purchased from M-System, or specified below, is used.
• CF Card
1. Manufacturer: Hagiwara Solutions
Model No.: MCF10P-xxxxS
Capacity: 128 MB through 1 GB
(CFI-xxxxDG ... discontinued)
2. Manufacturer: Apacer Technology
Model name: CFC III
Model No.: AP-CFxxxxE3ER-ETNDNRK
Capacity: 256 MB through 1 GB
  Part No.: 81.2A010.1H34C (256 MB)
    81.2B010.1H34C (512 MB)
    81.2E010.1H34C (1 GB)
(AP-CFxxxxE3ER-ETNDNR ... discontinued)
• SD Card (Compatible with 73VR1100 Ver.5.03.xx or later)
Manufacturer: Hagiwara Solutions
Model No.: NSD6-004GH (B21SEI
(NSDA-004GT, NSDA-004GL ... discontinued)
SD/CF Conversion Adapter is required to use SD card. There are some restrictions on using SD card. For details, refer to the instruction manual.
• SD/CF Conversion Adapter (operation confirmed):
  DeLOCK adaptor CF II to SDHC,SDXC
  Model: 61796 (purchased in the year of 2016)
Note: Refer to the data sheets of the respective models.

PACKAGE INCLUDES...
• 73VR Application Software CD (model: 73VRPAC2)
• Mounting brackets (two)
  (/HA: Not included for desktop type)

GENERAL SPECIFICATIONS
Construction: Panel mount type or desktop type
Degree of protection: IP65; applicable to the front panel of the recorder with single mounting according to the specified panel cutout (/HA: Desktop type cannot be mounted on a panel surface)
CONNECTION
Power input, alarm output, RUN contact output: M3 separable screw terminal  (torque 0.5 N·m)
Screw terminal: Nickel-plated steel (standard) or stainless steel
Ethernet: RJ-45 Modular Jack
RS-485: Euro type connector terminal
  Transmission media: Shielded twisted-pair cable (CPEV-S 0.9 dia.)
  Applicable wire size: 0.2 to 2.5 mm2 or AWG 24 to AWG 12 for both stranded and single core wires. stripped length 7 mm. Use pin terminals with stranded wires.
■ MATERIALS
Enclosure: Steel
Bezel: Flame-resistant resin (black)
Front filter: Transparent resin
Isolation: Alarm output to RUN output to power to Ethernet to FG or RS-485
INDICATORS
RUN output indicator LED
: Green light turns on in normal conditions; off in an abnormality.
Power indicator LED: Green light turns on when the power is supplied.
INTERFACE
Ethernet
: 10BASE-T / 100BASE-TX automatically switched; Conforms to IEEE 802 (10BASE-T) or IEEE 802.3 (100BASE-TX)
IP address: 192.168.0.1 (factory default setting)
Subnet mask: 255.255.255.0 (factory default setting)
Default gateway: None (factory default setting)
CF Card slot: Type I; for use with the cards’ operating voltage 3.3 V
USB: Conforms to Version 1.1
DISPLAY
Display device
: 5.5-inch TFT LCD
Display colors: 256
Resolution: 320 × 240 pixels
Pixel pitch: 0.12 × 0.35 mm
Note: The backlight can be replaced in M-System factory.
The LCD must be replaced at the same time.
ALARM / RUN OUTPUT
Rated load
: 250 V AC @ 0.5 A (cos ø = 1)
(For desktop type EU conformity: < 50 V AC)
30 V DC @ 0.5 A (resistive load)
Maximum switching voltage: 250 V AC or 30 V DC
Maximum switching power: 250 VA or 150 W
Minimum load: 1 V DC @ 1 mA
Mechanical life: 2 × 107 cycles (rate 300/min.)
External protection is recommended when driving an inductive load.
RUN output contact: ON in normal conditions; OFF in errors (CPU error, application errors)
Alarm output contact: Specified in the application software

EXTERNAL INTERFACE
Modbus RTU
Configuratio
n: Half-duplex, asynchronous, no procedure
Standard: Conforms to TIA/EIA RS-485-A
Max. transmission distance: 500 meters
Transfer rate: 38400 bps
Data bit: 8
Parity bit: Odd
Stop bit: 1
Max. node number: 15 (except the master)
Transmission media:
Shielded twisted-pair cable (CPEV-S φ0.9)
Terminating resistor: incorporated

INSTALLATION
Power input
AC:
 Approx. 15 VA at 100 V
 Approx. 20 VA at 240 V
DC: 8 W or 340 mA
Operating temperature: 0 to 50°C (32 to 122°F)
Display quality (e.g. decreased contrast) may deteriorate when the recorder is used for a long time in an environment exceeding 50°C. However, it is only a temporary phenomenon. When the recorder is back in normal temperature, full legibility is recovered. No damage in performance.
Operating humidity: 30 to 85 %RH (non-condensing)
Allowable dust particles: 0.1 mg/m2 (no conductive particles)
Corrosive gas: Not allowed
Mounting: Panel flush mounting (except desktop type)
Panel cutout dimensions: 137 × 137 mm (5.39”× 5.39”)
Weight: 1.7 kg (3.7 lb)
Caution: Use of UPS (switching time: without delay, output: sine waveforms) is recommended to prevent data loss or CF card damage by a loss of power during recording.

PERFORMANCE
Calendar clock accuracy: Monthly deviation 3 minutes at 25°C
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 500 V AC @ 1 minute
(alarm output to RUN output to power or FG or RS-485)
 AC powered:
2000 V AC @ 1 minute (power to FG or Ethernet or RS-485)
500 V AC @ 1 minute (FG or RS-485 to Ethernet)
 DC powered:
1250 V AC @ 1 minute (power to FG or Ethernet or RS-485)
500 V AC @ 1 minute (FG or RS-485 to Ethernet)

STANDARDS & APPROVALS
EU conformity:
(M2 AC power of desktop type does not conform to EU directive)
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
Low Voltage Directive
  EN 61010-1
  Installation Category II
  Pollution Degree 2
Alarm output to RUN output to power to FG or Ethernet or RS-485: Reinforced insulation (300 V)
RoHS Directive
  EN 50581

APPLICATION SOFTWARE CD
73VRPAC2 (included in the product package)
• 73VR1100 Builder Software: Model 73VR11BLD
Used to configure parameters on the PC.
- Parameter configurations can be downloaded to the recorder via Ethernet.
- Present setting on the 73VR1100 can be uploaded and displayed on the PC.
- Configuration files can be converted into CSV.
• 73VR Data Viewer: Model 73VRWV
Used to show and analyze recorded data on the PC.
- Data stored in the CF Card can be called up on the PC screen via the CF Card Reader.
- Data stored in the CF Card can be sent by FTP and called up on the PC screen.
- Various analyzing functions
- Data, alarm history and comment files can be converted into CSV.
• PC Recorder Software: Model MSR128-V6
The 73VR1100 data can be sampled and stored in real time via Ethernet by the MSR128-V6.
• Instruction Manuals
- 73VR1100 users manual
- 73VR11BLD users manual
- 73VRWV users manual
- MSR128-V6 users manual

PC REQUIREMENTS (provided by the user)

EXTERNAL VIEW

COMMUNICATION CABLE CONNECTIONS

CONNECTION DIAGRAM
Note: In order to improve EMC performance, bond the FG terminal to ground.
Caution: FG terminal is NOT a protective conductor terminal.

DIMENSIONS unit: mm (inch)

PANEL CUTOUT (unit: mm)
Usable panel thickness: 2 – 26 mm (0.08” – 1.02”)

SOFTWARE FUNCTIONS
NUMBER OF INPUT PEN POINTS
High speed mode
: 64 points
Normal mode: 128 points
Function pen points are included in the above figures.
TYPE OF I/O DEVICES
High speed mode
: R3-NE1
Normal mode: R1M-GH2, R1M-J3, R1M-A1, R1M-D1, R1M-P4, R1MS-GH3, R2M-2G3, R2M-2H3, RZMS-U9, R3-NE1, R3-NM1, R5-NE1, R5-NM1, R7E, R7M, 53U, IT60RE, IT40SRE, IT50SRE, IT60SRE
NUMBER OF I/O DEVICES
Ethernet
High speed mode
: 1 station
Normal mode: 2 stations; Max. 15 nodes are connectable to one 72EM2-M4 station.
RS-485: 15 nodes
DATA STORING METHOD
Normal: Recording is manually initiated and stopped. Data is continuously stored while the recording is on.
Auto: Recording is automatically initiated and stopped at a predefined time.
Event recording: The recorder detects an external event by trigger signal, and stores preset number of samples (max. 1200 respectively) before and after the moment of event.
Remote trigger: Data is automatically recorded while the external trigger condition (input) is true.
STORING RATE
High speed mode
: 100 msec.
Normal mode: 500 msec., 1, 2, 5, 10 seconds, 1 minute, 10 minutes (Actual storing rate depends upon the number of I/O devices. Contact M-System for more information.)
[Example] Max. number of I/O devices that ensures 500 msec. storing intervals under the following conditions:
Data cycle priority on alarm, RS-485 connection, no trigger or alarm setting
R1M-GH2: 10
RZMS-U9: 2
R3-NE1: 1 (128 channels, analog input only)
DATA STORAGE
Data file: Stores momentary values in the storing rate and their calculation result.
Alarm history file: Records time index information when alarms are triggered and reset.
Oldest data is overwritten with new data when the number of records reaches its limit.
Comment history file: Records comments written in trend views with time index. Oldest data is overwritten with new data when the number of records reaches 1000 files.
Configuration file: Stores the 73VR1100 setting.
File format: Binary
Oldest measured data is overwritten with new data or data recording is stopped when the card memory is full.
ALARM
• Analog Alarm
Alarm setpoints
: Max. 4 points per channel
Alarm type: High / Low
Deadband: Set in engineering unit values
Output: Remote output devices
• Discrete Alarm
Alarm type
: ON / OFF
Delay time: Selectable
Output: Remote output devices
• Data Storage: Trigger time, reset time, pen number and tag name, alarm message
Number of stored alarm events: Depends upon the CF Card capacity.
128 MB: 250 events
256 MB: 500 events
512 MB or 1 GB: 1000 events
CALCULATION FUNCTIONS
Function pen points
High speed mode
: 32 points
Normal mode: 32 or 64 points selectable
Operations
Arithmetic
: Addition/subtraction, Multiplication, Division
Logical: AND, OR, NOT, XOR
Mathematical: Square root extractor, Power
Accumulation: Analog accumulation, Pulse accumulation (per time unit)
Filter: Moving average, First order lag
Hold: Peak (maximum) hold (tracking increasing signal), Peak (minimum) hold (tracking decreasing signal)
F value: F value
Anemoscope (16 directions)
Alarm: Alarm trip can be programmed for calculated results.
DATA DISPLAY FUNCTIONS
• Trend View
Chart direction
: Perpendicular or horizontal
Number of pens displayed: 2, 4, 6, 8 per view
Number of display views: 4
Chart speed:(Chart speed is described as number of pixels to plot single data sample.)(pixel(s)/samples)
4, 1, 1/5, 1/32
1/160, 1/480 or 1/960 (Not selectable with 100 msec. storing rate)
Display rate:(Common setting to all views)
1, 2 or 5 sec.
Pen thickness: Normal and wide
Digital indicator: Shows momentary value.
Alarm indicator: Shows alarm status of the channels displayed on the screen.
Comment: Shows comments entered manually.
Scale: Linear and square root; Switchable to the engineering unit scale.
• Bargraph View
Bargraph direction
: Perpendicular or horizontal
Number of pens displayed: 2, 4, 6, 8 per view
Number of display views: 4
Display rate:(Common setting to all views)
1, 2 or 5 sec.
Digital indicator: Shows momentary value.
Alarm indicator: Shows alarm status of the channels displayed on the screen.
Scale: Linear and square root;
Switchable to the engineering unit scale.
• Overview
Number of pens displayed
: 2, 4, 6, 8, 16 per view
Number of display views: 64
Display rate:(Common setting to all views)
1, 2, or 5 sec.
Alarm indicator: Shows alarm status and date/time of the last alarm trip and reset for the channels displayed on the screen.
• Graphic View
Number of display views
: 2
Display rate:(Common setting to all views)
1, 2 or 5 sec.
Background image file format: .bmp
Background image size: 320 by 240 pixels
Background image color: 256
Number of components displayed: Max. 64 per view
• Retrieve View: Shows data stored in the CF Card.
Number of pens displayed: 2, 4, 6, 8 per view
Number of display views: 4
Data search: Scrolling the chart, specifying a specific time index, or searching by max./min. values.
• Alarm History View: Shows data stored in the alarm history file.
Number of displayed alarm events: 16
Number of display views: 1
Display update: Automatically updated by a new event
Data search: Scrolling the view or specifying a specific time index.
Jump: Scroll the view to an alarm event to show the relevant data on Retrieve View.
• Comment History View: Shows data stored in the comment history file.
Number of displayed alarm events: 16
Number of display views: 1
Data search: Scrolling the view or specifying a specific time index.
Jump: Scroll the view to a comment to show the relevant data on Retrieve View.

ETHERNET COMMUNICATION
• Dedicated Protocol
Real time communication
: Transmits specific data to a host PC installed with the PC Recorder Software (model: MSR128). Max. 2 hosts.
FTP communication: Transmits data stored in the CF Card using the FTP protocol to a host PC by the 73VR Data Viewer (model: 73VRWV) installed in it. Data can be transmitted even during recording.
Download, Upload: Software configurations created on the 73VR1100 Configuration Builder (model: 73VR11BLD) can be downloaded to the 73VR1100. The configuration set up on the 73VR1100 can be uploaded and displayed on the 73VR11BLD.
• Modbus Protocol
Protocol
: Modbus/TCP
Port No.: 502 (fixed)
IP address: Set on the recorder
Subnet mask: Set on the recorder
Default gateway: Set on the recorder
Max. number of 73VR1100 connected simultaneously: 2

OTHER FUNCTIONS
• Operation Lockout
With a password setting, unauthorized operations on the Trend View, Bargraph View and Overview can be locked out.
• Data File Used Volume Information
A bargraph with % indication is provided on the screen to show how much percent of the data file memory has been used up.
0 – 49 % used: Green bargraph
50 – 79 % used: Amber bargraph
80 – 100 % used: Red bargraph
• Hot Swapping of the CF Card
The CF Card is hot swappable: removable during data recording. However, there may be a slight disturbance in storing rate when the card is inserted.
• Screen Saver
The backlight is automatically turned off if the screen is untouched for a certain time period.
• Writing/Reading Setting
The recorder’s present setting can be stored in a USB flash-memory. Setting stored in the memory can be read in to the 73VR1100.

SELECTABLE REMOTE I/O MODULES

SYSTEM CONFIGURATION EXAMPLES

MG Co., Ltd.