·Some details are not shown. Please refer to specification sheets for all information.

PRP

Final Control Elements

SERVO-TOP II ELECTRONIC ACTUATOR
(rotary type; max. torque 200 N·m)

Functions & Features
• Control valve actuator drive
• I to I positioner incorporated
• Friendly user interface
• High resolution stepping motor
• Failsafe (safety operation) function optional
• Lloyd's Resister approved type available (Environmental categories ENV3)
 

MODEL: PRP–[1][2]–[3][4]

ORDERING INFORMATION
• Code number: PRP-[1][2]-[3][4]
Specify a code from below for each [1] through [4].
 (e.g. PRP-01A-L3/E)
Use Ordering Information Sheet (No. ESU-4823).
Factory setting (table below) will be used if not otherwise specified.

[1] TORQUE, OPERATION TIME
01: 100 N·m, 12 sec./90°
03: 100 N·m, 24 sec./90°
00: Refer to the torque explanation on the manual.
   Use specified operation time.
11: 200 N·m, 16 sec./90°
13: 200 N·m, 24 sec./90°
10: Refer to the torque explanation on the manual.
   Use specified operation time.

[2] INPUT
Current
A: 4 – 20 mA DC (Input resistance 250 Ω)
Voltage
6: 1 – 5 V DC (Input resistance 1 MΩ min.)

[3] POWER INPUT
AC Power
K3: 100 – 120 V AC
(Operational voltage range 90 – 132 V, 47 – 66 Hz)
L3: 200 – 240 V AC
(Operational voltage range 180 – 264 V, 47 – 66 Hz)

[4] OPTIONS
Failsafe Function
blank: Without
/E: With

RELATED PRODUCTS (Products sold separately)
• Programming Unit (model: PU-2x)
• Backup battery (model: PSN-BAT)

GENERAL SPECIFICATIONS
Degree of protection: IP66
Action: Reverse or direct or  (In "reverse" action, the output stem turns counterclockwise (seen from the indicator) with an input signal increase.)
Field selectable with DIP switches
Operation at input failure: Stem stop at full-open, full-close or hold position at input failure; field selectable with DIP switches
Minimum input signal
  Current input: ≥ 2.0 mA DC
  Voltage input: ≥ 0.5 V DC
Wiring conduits: G 1/2 female thread (two)
Terminal block: 7.62 mm pitch; M3 screw terminals (torque 0.8 N·m)
Housing material: Diecast aluminum
Coating: Baked acrylic resin
Drive: Stepping motor
Insulation class: E
Power control element: Power MOS-FET
Position detection: Potentiometer
Full-open and full-closed positions: -5 to +95°; minimum span 45°; field adjustable with control buttons
Full-closed signal adj.: 0 – 25 %
Full-open signal adj.: 75 – 100 %
Close side limiter adjustment: -5 – +25 %
Open side limiter adjustment: 75 – 105 %
Deadband adjustment: 0.1 – 5.0 % (Deadband width affects the resolution. See Resolution in Performance section.)
Restart limiting timer adjustment: 0 – 30 sec.
Opening/closing speed adjustment
•PRP-0: 8.5 to 125 sec./90°
•PRP-1: 16 to 125 sec./90°
Isolation: Signals to power to sequential signals to battery status (Option /E) to metallic housing
Fuse: 3 A (replaceable)
Protective functions: Error detection, abnormal temperature increase protection, motor preheat
Power indicator: Green LED turns on with power supplied.
Input indicator: Green LED turns on with normal input
Alarm indicator: Red LED turns on in error; blinks in 1-sec. intervals when abnormal temperature increase is detected.
Manual operation: Available (10 turns/90°)
User-configurable items:
Configurable with Programming unit (model: PU-2x)
•Output stem position at full-closed/open
•Opening/closing speed
•Closed/open side limiter
•Full-closed/open signal
•Split range and point
•Deadband
•Restart limiting timer
•Failsafe opening/closing speed (option /E)
•Failsafe target position (option /E)
BATTERY (failsafe function option)
Battery chemistry
: Nickel–cadmium
Battery life: Rechargeable up to 500 times; or 3 years, whichever is shorter, depending upon conditions of use
Drive capacity: Once
Charge method: Trickle charge after full rapid charge
Charge time: 180 minutes (completely discharged)
Power indicator: Red LED turns ON with the power supplied
Battery status indicator: Red LED turns ON with full charge; OFF with the power removed.
Charge indicator: Red LED turns ON during rapid charge

INPUT SPECIFICATIONS
DC Current: Resistor (2 W) incorporated
Forced Operation: External contact signal input terminals provided for compulsory opening or closing operation
Rating: 5 V DC @ 2.5 mA
Split Range: Specify split range type and split point.
Split range type: LO or HI
Split point: 30 – 70 %

OUTPUT SPECIFICATIONS
Position Signal: 4 – 20 mA DC
Load resistance: ≤ 300 Ω
Sequential Control Signal: "Full-open", "full-closed" and "alarm"
Open collector: 30 V DC @ 100 mA max.
Saturation voltage: 1 V DC
Failsafe Function (optional)
Battery status output
: ON with full charge; OFF with the power removed.
Open collector: 30 V DC @ 100 mA
Saturation voltage: 1 V DC

INSTALLATION
Power consumption: Approx. 180 VA
Stand-by consumption: Approx. 18 VA
Operating temperature: -20 to +55°C (-4 to +131°F)
Charge: 0 to 55°C (32 to 131°F)
When the ambient temperature is less than 0°C (32°F), the battery is not charged.
However, the ambient temperature reaches
within 0 to 55°C (32 to 131°F), the battery is automatically charged.
Operating humidity: 30 to 85 %RH (non-condensing)
Vibration: Passed test condition below
•Fixed frequency endurance test
 Acceleration: 2 G (19.6 m/s2)
 Frequency: at resonant frequency
 Endurance: 30 min.
 Direction: X, Y, Z
•Sweep endurance test
 Acceleration: 2 G (19.6 m/s2)
 Frequency: 10 to 1000 Hz
 Cycle: 20 cycles
 Rate: 1 Oct./min.
 Endurance: approx. 4 hr. 30 min.
 Direction: X, Y, Z
Mounting position: All directions
Do not mount the actuator with its output stem on the upside if the actuator is to be exposed to dripping water.
Weight: Approx. 10.8 kg (23.8 lb)
Approx. 12.1 kg (26.7 lb) with Option /E

PERFORMANCE
Resolution: 1/200 with 0.5 % deadband (factory setting);
1/1000 with 0.1 % deadband
Insulation resistance: ≥ 100 MΩ with 500 V DC (signal to power to sequential signals to battery status (Option /E) to metallic housing)
Dielectric strength: 2000 V AC @ 1 minute
(signal or metallic housing to power to battery status (Option /E) to sequential signals)
500 V AC @ 1 minute (signal to metallic housing)

FUNCTIONS
Error Detection
When the position signal is deviated from the input signal but the output stem is stuck due to overload or certain malfunction, the PRP repeats starting the motor at the maximum torque for several times.
If the stem is still stuck after that, the PRP outputs an alarm signal (LED turned ON) and stops power supply to the motor.
In order to reset the PRP, apply several times 0 % and 100 % input signals in turn, or turn off and on the power supply.
Abnormal Temperature Increase Protection
When the incorporated temperature sensor detects an abnormal temperature increase in the motor, the alarm LED blinks (repeating 0.5-sec. ON – 0.5-sec. OFF) and the power supply to the final control element motor is stopped until the temperature decreases to an acceptable level. The PRP is designed to resume automatically power supply to the motor. It takes longer to resume normal operation when ambient temperature is higher.
Restart Limiting Timer
This unit is equipped with a timer protecting the motor from overheating. The timer prevents the motor from restarting for a certain interval once the motor has been stopped within deadband.
When the high temperature protection is activated in a high temperature ambient, adjust the timer to a longer interval.
Motor Preheat Function
When this unit detects a temperature lower than 0°C or 32°F (approximate) on the surface of its motor, this unit supplies current to the motor in order to warm up and maintain its surface temperature at 5°C or 41°F (approximate).
Maintain the power supply ON when this unit is used in the ambient temperature below 0°C or 32°F.
• Resolution
The ratio that the stem of the unit rotates according to input signal.
E.g. Resolution is 1/200 for the specification that input signal is 4 to 20 mA, output stem 90°, direct or reverse action.  As the span of input signal is 16 mA (20 - 4 = 16 mA), when input signal is changed  by 0.08 mA step (16 mA / 200 = 0.08 mA), the output stem rotates 0.45° (90° / 200 = 0.45°).
(Even for output stem 45°setting, resolution is 1/200 = 0.45°step)
It is not true that input signal = output signal.
(Not input signal 4.00 mA DC = output signal 4.00 mA DC, there is difference around 0.04 mA DC.)

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY

MG Co., Ltd.