·Some details are not shown. Please refer to specification sheets for all information.

R8-DC4A

Remote I/O R8 Series

NPN TRANSISTOR OUTPUT MODULE
(with shortcircuit protection, 4 points)

Functions & Features
• 4-channel discrete output, compact size remote I/O module

MODEL: R8–DC4A[1]

ORDERING INFORMATION
• Code number: R8-DC4A[1]
Specify a code from below for [1].
  (e.g. R8-DC4A/Q)
• Specify the specification for option code /Q
  (e.g. /C01)

[1] OPTIONS
blank: none
/Q: With options (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating

RELATED PRODUCTS
• PC configurator software (model: R8CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS
Connection
 
Input: 4-pin e-CON connector
  Unit side connector XN2D-1474-S002 (Omron)
  Recommended cable side connector XN2A-1470 (Omron)
  Applicable wire size 0.08 - 0.5 mm2 (AWG28 - AWG20)
  Outer sheath diameter: max. 1.5 dia
  (The cable side connector is not included in the package.
   Refer to the specifications of the product.)
 Excitation supply, internal bus:
  Connected to internal bus connector
 Internal power: Supplied from internal bus connector
Isolation: Output or exc. supply to internal bus or internal power
Module address: With rotary switch
Output at the loss of communication: Selectable with the side DIP SW
Terminating resistor: Built-in (DIP Switch, default: disable)
Configuration mode: With DIP switches on the side panel
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Discrete output status indicators: Green LED; Refer to the instruction manual.

OUTPUT SPECIFICATIONS
Common: Negative common (NPN) per 4 points
Number of outputs: 4
Maximum outputs applicable at once: No limit (at 24 V DC)
Rated load voltage: 24 V DC ±10 %
Rated output current: 0.2 A per point
Residual voltage: ≤ 0.5 V
Leakage current: ≤ 0.1 mA
ON delay: ≤ 0.5 msec.
OFF delay: ≤ 1.5 msec.
Shortcircuit protection: Included
Overheat Protection Function: Included
(When driving an inductive load, connect a diode in parallel with the load.)

INSTALLATION
Max. current consumption: 100 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 60 g (2.12 oz)

PERFORMANCE
Data allocation: 1
Module addresses in use: 1
Power output (output terminal): Rated curent 1 A DC per channel; total: 2 A DC
Max. consumption current: 100 mA
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @ 1 minute
(output or exc. supply to internal bus or internal power to ground)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

EXTERNAL VIEW

OPERATING MODE SETTING

(*) Factory setting
Caution ! - SW4-1 through 4-6 are unused. Be sure to turn off unused ones.

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.