·Some details are not shown. Please refer to specification sheets for all information.

MDP-SP

Lightning Surge Protectors for
Electronics Equipment M-RESTER

LIGHTNING SURGE PROTECTOR FOR
LOW FREQUENCY USE

Functions & Features
• Designed specifically to protect frequency generating devices such like flowmeters and frequency transmitters from lightning surge damage that enters on the wiring between these instruments
• Absorbs surges only without affecting instrumentation signal
• No interruption of signal by unplugging the protector element

MODEL: MDP–SP[1]

ORDERING INFORMATION
• Code number: MDP-SP[1]
 Specify a code from below for [1].
(e.g. MDP-SP/A33/Q)
• Specify the specification for option code /Q
(e.g. /C01)

[1] OPTIONS (multiple selections)
DIN Rail Mounting Adapter
blank: Without
/A33: With adapter (model A-33)
Other Options
blank: none
/Q: Option other than the above (specify the specification)

SPECIFICATIONS OF OPTION: Q
COATING (For the detail, refer to M-System's web site.)
/C01: Silicone coating
/C02: Polyurethane coating
/C03: Rubber coating

GENERAL SPECIFICATIONS
Construction: Plug-in
Connection: M4 screw terminals (torque 0.8 N·m)
Screw terminal: Nickel-plated steel
Housing material: Flame-resistant resin (black)

INSTALLATION
Operating temperature: -5 to +55°C (23 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Surface or DIN rail
Weight: 140 g (0.31 lb), standard
165 g (0.36 lb), with DIN rail mounting adapter

PERFORMANCE
Max. continuous operating voltage (Uc): 
 B to C: ±14 V min.
 B or C to A: 14 V min.
 Line to earth: ±140 V min.
Voltage protection level (Up):
• @ 1 kV (100 A)
 2 to 3: ±30 V max. 
 2 or 3 to 1: 30 V max.
 Line to earth: ±650 V max.
• @ 2 kV (1 kA) 
 2 to 3: ±30 V max. 
 2 or 3 to 1: 30 V max.
 Line to earth: ±800 V max.
Response time: ≤ 0.1 μsec.
Leakage current:
 B to C: ≤ 10 μA @ ±14 V DC
 B or C to A: ≤ 10 μA @ 14 V DC
 Line to earth: ≤ 10 μA @ ±140 V DC
Max. discharge current (Imax): 5000 A (8 / 20 μs)
Nominal current (IN): 50 mA
Internal series resistance: 10 Ω ±10 %
Capacitance @ 1 MHz:
 Line to line:  ≤ 1000 pF
 Line to earth: ≤ 100 pF

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

Surge protection: IEC 61643-21
 (Categories C1, C2)

CONNECTION EXAMPLES

GROUNDING

EXTERNAL DIMENSIONS & TERMINAL ASSIGNMENTS unit: mm (inch)

MOUNTING REQUIREMENTS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.