·Some details are not shown. Please refer to specification sheets for all information.

R8-TS2

Remote I/O R8 Series

THERMOCOUPLE INPUT MODULE
(2 points, isolated)

Functions & Features
• Accepts direct input from an thermocouple and provides an isolated, linearized DC signal compact size remote I/O module

MODEL: R8–TS2

ORDERING INFORMATION
• Code number: R8-TS2

RELATED PRODUCTS
• PC configurator software (model: R8CFG)
Downloadable at M-System’s web site.
A dedicated cable is required to connect the module to the PC.  Please refer to the internet software download site or the users manual for the PC configurator for applicable cable types.

GENERAL SPECIFICATIONS
Connection
 
Input: 4-pin e-CON connector
  PWB connector XN2D-1474-S002 (Omron)
  Recommended cable connector XN2A-1470 (Omron)
  Applicable wire size 0.08 mm2 (AWG28) - 0.5 mm2 (AWG20)
  Outer sheath diameter: max. 1.5 dia
  (The cable connector is not included in the package.
   Refer to the specifications of the product.)
 Excitation supply, internal bus:
  Connected to internal bus connector
 Internal power: Supplied from internal bus connector
Isolation: Input 1 to input 2 to exc. supply to internal bus or internal power
Zero adjustments: -32000 - 32000 (PC programming)
Span adjustments: -32000 - 32000 (PC programming)
Configurator software can handle 100 - 200℃ as numerical value of 0 - 10000
Input sensor setting:DIP switches on the side or with PC
Burnout detection: Selectable with the side DIP SW
Linearization: Standard
Cold Junction Compensation: CJC sensor incorporated
Module address: With rotary switch
Converted data range:
•Engineering unit value (°C, K) × 10 (integer)
•Engineering unit value (°F)
Terminating resistor: Built-in (DIP Switch, default: disable)
Status indicator: Bi-color (red/green) LED; Refer to the instruction manual.
Input status indicators: Red LED; Refer to the instruction manual.

INPUT SPECIFICATIONS
Input resistance: 10kΩ minimum
Burnout sensing: 0.2 μA

INSTALLATION
Max. current consumption: 100 mA
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Atmosphere: No corrosive gas or heavy dust
Mounting: DIN rail
Weight: 60 g (2.12 oz)

PERFORMANCE
Conversion accuracy: ±1°C (±1.8°F) except ±2.0°C (±3.6°F) for B, R, S, C, PR
Conversion rate: 100 msec. per channel
Data allocation: 2
Module addresses in use: 1
Cold junction compensation error:
±3°C at 25 ±10°C
±5.4°F at 77 ±18°F
(The described accuracy may be partially not satisfied when the input temperature is below 0°C. Consult factory.)
Temp. coefficient: ±0.03 %/°C (±0.02 %/°F)
Burnout response time: ≤ 1 sec.
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength:
  1000 V AC @ 1 minute (input 1 to input 2 to exc. supply to internal bus or internal power to ground)

STANDARDS & APPROVALS
EU conformity:
EMC Directive 
  EMI EN 61000-6-4
  EMS EN 61000-6-2
RoHS Directive
  EN 50581

EXTERNAL VIEW

OPERATING MODE SETTING
(*) Factory setting
Caution ! - SW4-4 through 4-6 are unused. Be sure to turn off unused ones.

DIMENSIONS unit: mm (inch)

SCHEMATIC CIRCUITRY & CONNECTION DIAGRAM

MG Co., Ltd.